GE L60 Instruction Manual page 248

Line phase comparison system ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5.4 FLEXLOGIC
SETTING
FLEXELEMENT 1
FUNCTION:
Enabled = 1
Disabled = 0
SETTING
FLEXELEMENT 1 BLK:
Off = 0
SETTINGS
FLEXELEMENT 1 +IN:
Actual Value
FLEXELEMENT 1 -IN:
Actual Value
The
FLEXELEMENT 1 +IN
this setting is set to "Off". For proper operation of the element at least one input must be selected. Otherwise, the element
5
will not assert its output operands.
This
FLEXELEMENT 1 –IN
this setting is set to "Off". For proper operation of the element at least one input must be selected. Otherwise, the element
will not assert its output operands. This input should be used to invert the signal if needed for convenience, or to make the
element respond to a differential signal such as for a top-bottom oil temperature differential alarm. The element will not
operate if the two input signals are of different types, for example if one tries to use active power and phase angle to build
the effective operating signal.
The element responds directly to the differential signal if the
ment responds to the absolute value of the differential signal if this setting is set to "Absolute". Sample applications for the
"Absolute" setting include monitoring the angular difference between two phasors with a symmetrical limit angle in both
directions; monitoring power regardless of its direction, or monitoring a trend regardless of whether the signal increases of
decreases.
The element responds directly to its operating signal – as defined by the
ELEMENT 1 INPUT MODE
rate of change of its operating signal if the
and
MENT 1 dt UNIT
FLEXELEMENT 1 dt
The
FLEXELEMENT 1 DIRECTION
following figure explains the application of the
settings.
TERESIS
5-120
SETTINGS
FLEXELEMENT 1 INPUT
MODE:
FLEXELEMENT 1 COMP
MODE:
FLEXELEMENT 1
DIRECTION:
FLEXELEMENT 1 PICKUP:
FLEXELEMENT 1 INPUT
AND
HYSTERESIS:
FLEXELEMENT 1 dt UNIT:
FLEXELEMENT 1 dt:
RUN
+
-
ACTUAL VALUE
FlexElement 1 OpSig
Figure 5–44: FLEXELEMENT SCHEME LOGIC
setting specifies the first (non-inverted) input to the FlexElement. Zero is assumed as the input if
setting specifies the second (inverted) input to the FlexElement. Zero is assumed as the input if
settings – if the
FLEXELEMENT 1 COMP MODE
FLEXELEMENT 1 COMP MODE
settings specify how the rate of change is derived.
setting enables the relay to respond to either high or low values of the operating signal. The
FLEXELEMENT 1 DIRECTION
L60 Line Phase Comparison System
SETTINGS
FLEXELEMENT 1 PKP
DELAY:
FLEXELEMENT 1 RST
DELAY:
t
PKP
t
RST
setting is set to "Signed". The ele-
FLEXELEMENT 1 INPUT MODE
FLEXELEMENT 1 +IN
setting is set to "Level". The element responds to the
setting is set to "Delta". In this case the
,
FLEXELEMENT 1 PICKUP
5 SETTINGS
FLEXLOGIC OPERANDS
FxE 1 OP
FxE 1 DPO
FxE 1 PKP
842004A3.CDR
,
and
FLEXELEMENT 1 –IN
FLEX-
FLEXELE-
and
FLEXELEMENT 1 HYS-
GE Multilin