Records; Fault Reports; Event Records - GE L60 Instruction Manual

Line phase comparison system ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

6 ACTUAL VALUES

6.4RECORDS


PATH: ACTUAL VALUES
RECORDS
NO FAULTS TO REPORT
or
 FAULT REPORT 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The latest 15 fault reports can be stored. The most recent fault location calculation (when applicable) is displayed in this
menu, along with the date and time stamp of the event which triggered the calculation. See the

menu for assigning the source and trigger for fault calculations. Refer to the
SETUP

FAULT REPORTS

menu for manual clearing of the fault reports and to the
CLEAR RECORDS
menu for automated clearing of the fault reports.
RECORDS

PATH: ACTUAL VALUES
RECORDS
 EVENT RECORDS
MESSAGE
MESSAGE
MESSAGE
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. See the
COMMANDS
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.
GE Multilin
FAULT REPORTS
FAULT REPORT 1(15)
FAULT 1
LINE ID: SRC 1
FAULT 1
DATE:
2000/08/11
FAULT 1
TIME:
00:00:00.000000
FAULT 1
TYPE:
ABG
FAULT 1
LOCATION
00.0 km
FAULT 1
RECLOSE
SHOT: 0


EVENT RECORDS

EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
POWER ON
EVENT: 2
POWER OFF
EVENT: 1
EVENTS CLEARED
menu for clearing event records.
CLEAR RECORDS
L60 Line Phase Comparison System
6.4.1 FAULT REPORTS
Range: SRC 1, SRC 2
Range: YYYY/MM/DD
Range: HH:MM:SS.ssssss
Range: not available if the source VTs are in the "Delta"
configuration
Range: not available if the source VTs are in the "Delta"
configuration
Range: where applicable
SETTINGS
SETTINGS
PRODUCT SETUP
6.4.2 EVENT RECORDS
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
Date and Time Stamps
6.4 RECORDS
PRODUCT

COMMANDS

CLEAR RELAY
6
6-21

Advertisement

Table of Contents
loading

Table of Contents