GE L60 Instruction Manual page 268

Line phase comparison system ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
h) POSITIVE-SEQUENCE OVERCURRENT FAULT DETECTION

PATH: SETTINGS
GROUPED ELEMENTS

POSITIVE-SEQUENCE CURRENT
 POSITIVE-SEQUENCE
 CURRENT
The positive-sequence overcurrent advanced fault detector element responds to the increment of the magnitude of the pos-
itive-sequence current over a specified threshold. Thresholds are provided for low-set control of keying and high-set opera-
tion control of tripping.
The following settings are available.
POS SEQ I_1 FD FUNCTION: This setting enables or disables the positive-sequence overcurrent fault detection. Note
5
that all fault detectors operate in parallel with the 87PC function. To effectively disable the overcurrent fault detectors
under the main 87PC menu, set their threshold very high.
POS SEQ I_1 FDL PICKUP: This setting specifies the pickup of the low-set stage of the element used to control the
key operation. The nominal current of the phase CT bank of the relay is 1 pu.
POS SEQ I_1 FDH PICKUP: This setting specifies the pickup of the high-set stage of the element used to control the
trip operation. The nominal current of the phase CT bank of the relay is 1 pu.
POS SEQ I_1 BLK: The fault detector is hard-wired to the 87PC scheme. It can be disabled permanently using the
function setting or blocked temporarily with this setting. This setting selects a FlexLogic operand that blocks this fault
detector when asserted.
POS SEQ I_1 FD TARGET: This setting controls targets of the positive-sequence overcurrent advanced fault detector
function. These targets operate independently from the 87PC targets.
POS SEQ I_1 FD EVENTS: This setting controls event recording of the positive-sequence overcurrent advanced fault
detector function. These events are logged independently from the 87PC events.
SETTINGS
POS SEQ I_1 FD FUNCTION
Disabled = 0
POS SEQ I_1 BLOCK
FAST MEASUREMENTS
F1 PHASE CT BANK
Positive-sequence
L1 PHASE CT BANK
Positive-sequence
Figure 5–54: POSITIVE-SEQUENCE OVERCURRENT ADVANCED FAULT DETECTOR LOGIC
5-140
PHASE COMPARISON ELEMENTS
POS SEQ I_1 FD
FUNCTION: Disabled
POS SEQ I_1 FDL
MESSAGE
PICKUP: 0.10 pu
POS SEQ I_1 FDH
MESSAGE
PICKUP: 0.50 pu
POS SEQ I_1 BLK:
MESSAGE
Off
POS SEQ I_1 FD
MESSAGE
TARGET: Self-reset
POS SEQ I_1 FD
MESSAGE
EVENTS: Disabled
Enabled = 1
AND
SETTINGS
Off = 0
POS SEQ I_1 FDL PICKUP
POS SEQ I_1 FDH PICKUP
RUN
> (FDL PICKUP) / 4
current I_1
> (FDH PICKUP) / 4
> (FDL PICKUP) / 4
current I_1
> (FDH PICKUP) / 4
Σ
L60 Line Phase Comparison System

ADVANCED FAULT DETECTORS
Range: Disabled, Enabled
Range: 0.20 to 5.00 pu in steps of 0.01
Range: 0.50 to 15.00 pu in steps of 0.01
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
To square pulse
and transmit logic
OR
OR
> FDL PICKUP
> FDH PICKUP
5 SETTINGS
Hardwired to the
87PC function
FLEXLOGIC OPERANDS
87PC I_1 FDL OP
AND
87PC I_1 FDH OP
AND
831031A2.CDR
GE Multilin