5.2 PRODUCT SETUP
# Management authorization
BEGIN-VENDOR
# Role ID
ATTRIBUTE
# GE-UR-ROLE values
VALUE GE-UR-Role
VALUE GE-UR-Role
VALUE GE-UR-Role
VALUE GE-UR-Role
VALUE GE-UR-Role
END-VENDOR
#############################################################
f. In the dictionary file in the <Path_to_Radius>\etc\raddb folder, add the following line.
$INCLUDE dictionary.ge
5
For example, the file can look like the following:
$INCLUDE ../shareéfreeradius/dictionary
$INCLUDE dictionary.ge
g. For the first start, run the RADIUS server in debug mode by entering <Path_to_Radius>/start_radiusd_debug.bat
h. Set up the RADIUS parameters on the UR as follows. Access Device > Settings > Product Setup > Security. Con-
figure the IP address and ports for the RADIUS server. Leave the GE vendor ID field at the default of 2910. Update the
RADIUS shared secret as specified in the clients.conf file.
3.
On the RADIUS server, configure the user accounts. Do not use the five pre-defined roles as user names (Administra-
tor, Supervisor, Engineer, Operator, Observer) in the RADIUS server. If you do, the UR relay automatically provides the
authentication from the device.
4.
In the EnerVista software, choose server authentication and log in using the user name and password configured on
the RADIUS server for server authentication login.
5.
After making any required changes, log out using the Commands > Relay Maintenance > Security menu.
For all user roles except Observer, only one instance can be logged in at one time, for both login by
front panel and software.
When changing settings offline, ensure that only settings permitted by the role that performs the set-
tings download are changed because only those changes are applied.
Targets refer to errors display on the front panel or the Targets panel in the EnerVista software. User accounts of Adminis-
trator, Engineer, and Factory Service can reset the targets using the reset key.
To reset targets:
1.
Log in as Administrator, Engineer, and Factory Service and make the changes. To reset the security-related self-test or
authentication lockout, log in as Administrator or Supervisor and execute a clear security command under Commands
> Security > Clear Security.
5-14
GE
GE-UR-Role
1
integer
Administrator
1
Supervisor
2
Engineer
3
Operator
4
Observer
5
GE
L60 Line Phase Comparison System
5 SETTINGS