5.2 PRODUCT SETUP
i) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
IEC 61850 PROTOCOL
5
The L60 Line Phase Comparison System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details.
IEC 61850 messaging can form part of protection schemes. Consider 61850 settings with the same criticality as
protection element settings. To ensure reliable performance of protection schemes utilizing 61850 messaging, it
can be desirable to route 61850 traffic on a separate port from SCADA communications, or to use redundant, inde-
NOTE
pendent ports, and a high speed network recovery method, such as PRP.
The L60 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over Ethernet. The L60 operates as an IEC 61850 server. The Remote inputs and outputs
section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
GSSE / GOOSE
CONFIGURATION
The main transmission menu is shown below:
5-32
COMMUNICATIONS
GSSE / GOOSE
CONFIGURATION
SERVER
MESSAGE
CONFIGURATION
IEC 61850 LOGICAL
MESSAGE
NODE NAME PREFIXES
MMXU DEADBANDS
MESSAGE
GGIO1 STATUS
MESSAGE
CONFIGURATION
GGIO2 CONTROL
MESSAGE
CONFIGURATION
GGIO4 ANALOG
MESSAGE
CONFIGURATION
GGIO5 UINTEGER
MESSAGE
CONFIGURATION
REPORT CONTROL
MESSAGE
CONFIGURATION
XCBR
MESSAGE
CONFIGURATION
XSWI
MESSAGE
CONFIGURATION
COMMUNICATIONS
TRANSMISSION
RECEPTION
MESSAGE
L60 Line Phase Comparison System
IEC 61850 PROTOCOL
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
5 SETTINGS
GE Multilin