5.2 PRODUCT SETUP
Selected records can be cleared from user-programmable conditions with FlexLogic operands. Assigning user-programma-
ble pushbuttons to clear specific records are typical applications for these commands. Since the L60 responds to rising
edges of the configured FlexLogic operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, the following settings should be applied.
1.
Assign the clear demand function to pushbutton 1 by making the following change in the
CLEAR RELAY RECORDS
CLEAR DEMAND:
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
PUSHBUTTON 1 FUNCTION:
PUSHBTN 1 DROP-OUT TIME:
5
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
5-22
RESET UNAUTH ACCESS:
MESSAGE
Off
CLEAR DIR I/O STATS:
MESSAGE
Off
menu:
"
"
PUSHBUTTON 1 ON
"Self-reset"
"0.20 s"
COMMUNICATIONS
SERIAL PORTS
NETWORK
MESSAGE
MODBUS PROTOCOL
MESSAGE
DNP PROTOCOL
MESSAGE
DNP / IEC104
MESSAGE
POINT LISTS
IEC 61850 PROTOCOL
MESSAGE
WEB SERVER
MESSAGE
HTTP PROTOCOL
TFTP PROTOCOL
MESSAGE
IEC 60870-5-104
MESSAGE
PROTOCOL
L60 Line Phase Comparison System
Range: FlexLogic operand
Range: FlexLogic operand.
Valid only for units with Direct I/O module.
menu:
USER PUSHBUTTON 1
See below.
See page 5–25.
See page 5–26.
See page 5–27.
See page 5–30.
See page 5–32.
See page 5–45.
See page 5–46.
See page 5–46.
5 SETTINGS
SETTINGS
PRODUCT SETUP
SETTINGS
PRODUCT
5.2.5 COMMUNICATIONS