GE L60 Instruction Manual page 430

Line phase comparison system ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5.8 TRANSDUCER INPUTS AND OUTPUTS
Table 5–31: RTD TEMPERATURE VS. RESISTANCE
TEMPERATURE
°C
°F
–50
–58
–40
–40
–30
–22
–20
–4
–10
14
0
32
10
50
20
68
30
86
40
104
50
122
60
140
70
158
80
176
90
194
100
212
110
230
5
120
248
130
266
140
284
150
302
160
320
170
338
180
356
190
374
200
392
210
410
220
428
230
446
240
464
250
482
5-302
RESISTANCE (IN OHMS)
100 Ω PT
120 Ω NI
100 Ω NI
(DIN 43760)
80.31
86.17
71.81
84.27
92.76
77.30
88.22
99.41
82.84
92.16
106.15
88.45
96.09
113.00
94.17
100.00
120.00
100.00
103.90
127.17
105.97
107.79
134.52
112.10
111.67
142.06
118.38
115.54
149.79
124.82
119.39
157.74
131.45
123.24
165.90
138.25
127.07
174.25
145.20
130.89
182.84
152.37
134.70
191.64
159.70
138.50
200.64
167.20
142.29
209.85
174.87
146.06
219.29
182.75
149.82
228.96
190.80
153.58
238.85
199.04
157.32
248.95
207.45
161.04
259.30
216.08
164.76
269.91
224.92
168.47
280.77
233.97
172.46
291.96
243.30
175.84
303.46
252.88
179.51
315.31
262.76
183.17
327.54
272.94
186.82
340.14
283.45
190.45
353.14
294.28
194.08
366.53
305.44
L60 Line Phase Comparison System
10 Ω CU
7.10
7.49
7.88
8.26
8.65
9.04
9.42
9.81
10.19
10.58
10.97
11.35
11.74
12.12
12.51
12.90
13.28
13.67
14.06
14.44
14.83
15.22
15.61
16.00
16.39
16.78
17.17
17.56
17.95
18.34
18.73
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents