Actual signals

The following table includes the descriptions of all actual signal.
Actual signals
No.
Name/Value

01 OPERATING DATA

0101
SPEED & DIR
0102
SPEED
0103
OUTPUT FREQ
0104
CURRENT
0105
TORQUE
0106
POWER
0107
DC BUS VOLTAGE
0109
OUTPUT VOLTAGE
0110
DRIVE TEMP
0111
EXTERNAL REF 1
0112
EXTERNAL REF 2
0113
CTRL LOCATION
0114
RUN TIME (R)
0115
KWH COUNTER (R)
0120
AI1
0121
POT
0137
PROCESS VAR 1
0138
PROCESS VAR 2
0139
PROCESS VAR 3
0140
RUN TIME
0141
MWH COUNTER
0142
REVOLUTION CNTR
0143
DRIVE ON TIME HI
0144
DRIVE ON TIME LO
0160
DI 1-5 STATUS
0161
PULSE INPUT FREQ
0162
RO STATUS
Actual signals and parameters
Description
Basic signals for monitoring the drive (read-only).
For actual signal supervision, see parameter group
For selection of an actual signal to be displayed on the control panel, see parameter
group
34 PANEL
DISPLAY.
Calculated motor speed in rpm. A negative value indicates reverse direction.
Calculated motor speed in rpm.
Calculated drive output frequency in Hz. (Shown by default on the panel Output mode
display.)
Measured motor current in A
Calculated motor torque in percent of the motor nominal torque
Measured motor power in kW
Measured intermediate circuit voltage in VDC
Calculated motor voltage in VAC
Measured IGBT temperature in °C
External reference REF1 in Hz
External reference REF2 in percent. 100% equals the maximum motor speed.
Active control location. (0) LOCAL; (1) EXT1; (2) EXT2.
Elapsed drive running time counter (hours). The counter can be reset by pressing the UP
and DOWN buttons simultaneously when the control panel is in Parameter mode.
kWh counter. The counter can be reset by pressing UP and DOWN buttons
simultaneously when the control panel is in Parameter mode.
Relative value of analog input AI1 in percent
Potentiometer value in percent
Process variable 1 defined by parameter group
Process variable 2 defined by parameter group
Process variable 3 defined by parameter group
Elapsed time counter (thousands of hours). Runs when the drive is running. Counter
cannot be reset.
MWh counter. Counter cannot be reset.
Motor revolution counter (millions of revolutions). The counter can be reset by pressing
the UP and DOWN buttons simultaneously when the control panel is in Parameter mode.
Drive control board power-on time in days. Counter cannot be reset.
Drive control board power-on time in 2 second ticks (30 ticks = 60 seconds). Counter
cannot be reset.
Status of digital inputs. Example: 10000 = DI1 is on, DI2...DI5 are off.
Value of frequency input in Hz
Status of relay output. 1 = RO is energised, 0 = RO is de-energized.