Parameters in the Long Parameter mode
Index Name/Selection
16 SYSTEM
CONTROLS
1601
RUN ENABLE
0 = NOT SEL
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
-1 = DI1(INV)
-2 = DI2(INV)
-3 = DI3(INV)
-4 = DI4(INV)
-5 = DI5(INV)
1602
PARAMETER LOCK
0 = LOCKED
1 = OPEN
2 = NOT SAVED
1603
PASS CODE
0...65535
1604
FAULT RESET SEL
0 = KEYPAD
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
7 = START/STOP
-1 = DI1(INV)
-2 = DI2(INV)
Description
Run Enable, parameter lock etc.
Selects a source for the external Run Enable signal.
Allows the drive to start without an external Run Enable signal.
External signal required through digital input DI1. 1 = Run Enable. If Run
Enable signal is switched off, the drive will not start or coasts to stop if it is
running.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
External signal required through inverted digital input DI1. 0 = Run Enable.
If Run Enable signal is switched on, the drive will not start or coasts to stop if
it is running.
See selection DI1(INV)
See selection DI1(INV)
See selection DI1(INV)
See selection DI1(INV)
Selects the state of the parameter lock. The lock prevents parameter
changing from control panel.
Parameter values cannot be changed from the control panel. The lock can be
opened by entering the valid code to parameter
The lock does not prevent parameter changes made by macros.
The lock is open. Parameter values can be changed.
Parameter changes made by control panel are not stored into the permanent
memory. To store changed parameter values, set parameter
SAVE value to SAVE.
Selects the pass code for the parameter lock (see parameter
PARAMETER LOCK).
Pass code. Setting 358 opens the lock. The value reverts back to 0
automatically.
Selects the source for the fault reset signal. The signal resets the drive after
a fault trip if the cause of the fault no longer exists.
Fault reset only from the control panel
Reset through digital input DI1 (reset by a rising edge of DI1) or by control
panel
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Reset along with the stop signal received through a digital input, or by control
panel.
Reset through inverted digital input DI1 (reset by a falling edge of DI1) or by
control panel
See selection DI1(INV).
1603
PASS CODE.
1607
PARAM
1602
Actual signals and parameters
81
Def
0 = NOT SEL
1 = OPEN
0
0 = KEYPAD