Select - ABB ACS150 User Manual

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

80
Parameters in the Long Parameter mode
Index Name/Selection
7 = STARTED
8 = SUPRV 1 OVER
9 = SUPRV 1 UNDER
10 = SUPRV 2 OVER
11 = SUPRV 2 UNDER See selection SUPRV 2 OVER.
12 = SUPRV 3 OVER
13 = SUPRV 3
UNDER
14 = AT SET POINT
15 = FAULT(RST)
16 = FLT/ALARM
17 = EXT CTRL
18 = REF 2 SEL
19 = CONST FREQ
20 = REF LOSS
21 = OVERCURRENT Alarm/Fault by overcurrent protection function
22 = OVERVOLTAGE
23 = DRIVE TEMP
24 =UNDERVOLTAGE Alarm/Fault by undervoltage protection function
25 = AI1 LOSS
27 = MOTOR TEMP
28 = STALL
29 = UNDERLOAD
33 = FLUX READY
1404
RO1 ON DELAY
0.0...3600.0 s
1405
RO1 OFF DELAY
0.0...3600.0 s
Actual signals and parameters
Description
The drive has received a start command. Relay is energized even if Run
Enable signal is off. Relay is de-energized when drive receives a stop
command or a fault occurs.
Status according to supervision parameters 3201...3203.
See selection SUPRV 1 OVER.
Status according to supervision parameters 3204...3206.
Status according to supervision parameters 3207...3209.
See selection SUPRV 3 OVER.
Output frequency is equal to the reference frequency.
Fault. Automatic reset after the autoreset delay. See parameter group
31 AUTOMATIC
RESET.
Fault or alarm
Drive is under external control.
External reference REF2 is in use.
A constant speed is in use. See parameter group
Reference or active control location is lost.
Alarm/Fault by overvoltage protection function
Alarm/Fault by drive overtemperature protection function
Analog input AI1 signal is lost.
Alarm/Fault by motor overtemperature protection function. See parameter
3005
MOT THERM PROT.
Alarm/Fault by stall protection function. See parameter
FUNCTION.
Alarm/Fault by underload protection function. See parameter
UNDERLOAD FUNC.
Motor is magnetised and able to supply nominal torque.
Defines the operation delay for relay output RO.
Delay time. The figure below illustrates the operation (on) and release (off)
delays for relay output RO.
Control event
Relay status
Defines the release delay for relay output RO.
Delay time. See the figure for parameter
12 CONSTANT
1404 ON DELAY 1405 OFF DELAY
1404
RO1 ON DELAY.
Def
SPEEDS.
3010
STALL
3013
0
0