Application Macros; What This Chapter Contains; Overview Of Macros; Select - ABB ACS150 User Manual

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

Application macros

What this chapter contains

The chapter describes the application macros. For each macro, there is a wiring
diagram showing the default control connections (digital and analog I/O).

Overview of macros

Application macros are preprogrammed parameter sets. While starting up the drive,
the user selects the macro best suited for the purpose with parameter
MACRO.
The ACS150 has five application macros. The table below contains a summary of
the macros and describes suitable applications.
Macro
ABB Standard
3-wire
Alternate
Motor
Potentiometer
Hand/Auto
Suitable applications
Ordinary speed control applications where no, one, two or three constant speeds
are used. Start/stop is controlled with one digital input (level start and stop). It is
possible to switch between two acceleration and deceleration times.
Ordinary speed control applications where no, one, two or three constant speeds
are used. The drive is started and stopped with push buttons.
Speed control applications where no, one, two or three constant speeds are used.
Start, stop and direction are controlled by two digital inputs (combination of the
input states determines the operation).
Speed control applications where no or one constant speed is used. The speed is
controlled by two digital inputs (increase / decrease / keep unchanged).
Speed control applications where switching between two control devices is
needed. Some control signal terminals are reserved to one device, the rest for the
other. One digital input selects between the terminals (devices) in use.
57
9902
APPLIC
Application macros

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs350

Table of Contents