Parameters in the Long Parameter mode
Index Name/Selection
3012
STALL TIME
10...400 s
3013
UNDERLOAD FUNC
0 = NOT SEL
1 = FAULT
2 = ALARM
3014
UNDERLOAD TIME
10...400 s
3015
UNDERLOAD CURVE Selects the load curve for the underload function. See parameter
1...5
3016
SUPPLY PHASE
0 = FAULT
1 = LIMIT/ALARM
Actual signals and parameters
Description
Defines the time for the stall function. See parameter
FUNCTION.
Time
Selects how the drive reacts to underload. The protection wakes up if
- the motor torque falls below the curve selected by parameter
UNDERLOAD CURVE,
- output frequency is higher than 10% of the nominal motor frequency and
- the above conditions have been valid longer than the time set by parameter
3014
UNDERLOAD TIME.
Protection is inactive.
The drive trips on fault UNDERLOAD (code: F0017) and the motor coasts to
a stop.
The drive generates alarm UNDERLOAD (code: A2011).
Defines the time limit for the underload function. See parameter
UNDERLOAD FUNC.
Time limit
UNDERLOAD FUNC.
T
= nominal torque of the motor
M
ƒ
= nominal frequency of the motor (par. 9907)
N
T
M
(%)
Underload curve types
80
60
40
20
0
Number of the load curve
Selects how the drive reacts to supply phase loss, i.e. when DC voltage
ripple is excessive.
The drive trips on fault INPUT PHASE LOSS (code: F0022) and the motor
coasts to a stop when the DC voltage ripple exceeds 14% of the nominal DC
voltage.
Drive output current is limited and alarm INPUT PHASE LOSS (code: A2026)
is generated when the DC voltage ripple exceeds 14% of the nominal DC
voltage.
There is a 10 s delay between the activation of the alarm and the output
current limitation. The current is limited until the ripple drops under the
minimum limit, 0.3 · I
.
hd
3010
STALL
3
2
1
5
4
2.4 · ƒ
ƒ
N
Def
20
0 = NOT SEL
3015
3013
20
3013
1
70%
50%
30%
f
N
0 = FAULT