ABB ACS150 User Manual page 137

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

Note: Larger fuses must not be used.
Type
Fuses
gG
ACS350-
x = E/U
A
1-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
01x-02A4-2
10
01x-04A7-2
16
1)
01x-06A7-2
16/20
1)
01x-07A5-2
20/25
1)
01x-09A8-2
25/35
3-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
03x-02A4-2
10
03x-03A5-2
10
03x-04A7-2
10
03x-06A7-2
16
03x-07A5-2
16
03x-09A8-2
16
03x-13A3-2
25
03x-17A6-2
25
03x-24A4-2
63
03x-31A0-2
80
03x-46A2-2
100
3-phase U
= 380...480 V (380, 400, 415, 440, 460, 480 V)
N
03x-01A2-4
10
03x-01A9-4
10
03x-02A4-4
10
03x-03A3-4
10
03x-04A1-4
16
03x-05A6-4
16
03x-07A3-4
16
03x-08A8-4
20
03x-12A5-4
25
03x-15A6-4
35
03x-23A1-4
50
03x-31A0-4
80
03x-38A0-4
100
03x-44A0-4
100
1)
If 50% overload capacity is needed, use the bigger fuse alternative.
UL Class
Supply
T (600 V)
(U1, V1, W1)
2
A
mm
AWG
10
2.5
14
20
2.5
14
25
2.5
10
30
2.5
10
35
6
10
10
2.5
14
10
2.5
14
15
2.5
14
15
2.5
12
15
2.5
12
20
2.5
12
30
6
10
35
6
10
60
10
80
16
100
25
10
2.5
14
10
2.5
14
10
2.5
14
10
2.5
12
15
2.5
12
15
2.5
12
20
2.5
12
25
2.5
12
30
6
10
35
6
50
10
80
16
100
16
100
25
Size of CU conductor in cablings
Motor
(U2, V2, W2)
2
mm
AWG
0.75
18
0.75
18
1.5
14
1.5
14
2.5
12
0.75
18
0.75
18
0.75
18
1.5
14
1.5
14
2.5
12
6
10
6
10
8
10
8
6
16
6
2
25
2
0.75
18
0.75
18
0.75
18
0.75
18
0.75
18
1.5
14
1.5
14
2.5
12
6
10
8
6
8
8
10
8
6
16
6
4
16
4
4
25
4
PE
(BRK+ and BRK-)
2
2
mm
AWG
mm
2.5
14
2.5
2.5
14
2.5
2.5
10
2.5
2.5
10
2.5
6
10
6
2.5
14
2.5
2.5
14
2.5
2.5
14
2.5
2.5
12
2.5
2.5
12
2.5
2.5
12
2.5
6
10
2.5
6
10
2.5
10
8
6
16
6
10
16
4
10
2.5
14
2.5
2.5
14
2.5
2.5
14
2.5
2.5
12
2.5
2.5
12
2.5
2.5
12
2.5
2.5
12
2.5
2.5
12
2.5
6
10
2.5
6
8
2.5
10
8
6
16
6
10
16
4
10
16
4
10
Technical data
117
Brake
AWG
14
14
12
12
12
14
14
14
12
12
12
12
12
10
8
8
14
14
14
12
12
12
12
12
12
12
10
8
8
8
00353783.xls H