ABB ACS150 User Manual page 129

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

CODE
FAULT
EARTH FAULT
F0016
(programmable
fault function 3017)
UNDERLOAD
F0017
(programmable
fault function
3013...3015)
THERM FAIL
F0018
CURR MEAS
F0021
INPUT PHASE
F0022
LOSS
(programmable
fault function 3016)
DRIVE ID
F0026
CONFIG FILE
F0027
OUTP WIRING
F0035
(programmable
fault function 3023)
INCOMPATIBLE
F0036
SW
SERF CORRUPT
F0101
SERF MACRO
F0103
DSP T1
F0201
OVERLOAD
DSP T2
F0202
OVERLOAD
DSP T3
F0203
OVERLOAD
DSP STACK
F0204
ERROR
MMIO ID ERROR
F0206
PAR HZRPM
F1000
PAR AI SCALE
F1003
CAUSE
Drive has detected earth (ground)
fault in motor or motor cable.
Motor load is too low due to e.g.
release mechanism in driven
equipment.
Drive internal fault. Thermistor
used for drive internal temperature
measurement is open or
short-circuited.
Drive internal fault. Current
measurement is out of range.
Intermediate circuit DC voltage is
oscillating due to missing input
power line phase or blown fuse.
Fault trip occurs when DC voltage
ripple exceeds 14% of nominal DC
voltage.
Internal drive ID fault
Internal configuration file error
Incorrect input power and motor
cable connection (i.e. input power
cable is connected to drive motor
connection).
Loaded software is not
compatible.
Corrupted Serial Flash chip file
system
Active macro file missing from
Serial Flash chip
System error
Internal I/O Control board (MMIO)
fault
Incorrect speed/frequency limit
parameter setting
Incorrect analog input AI signal
scaling
WHAT TO DO
Check motor.
Check fault function parameter setting.
Check motor cable. Motor cable length must not
exceed maximum specifications. See section
connection
on page 119.
Check for problem in driven equipment.
Check fault function parameter settings.
Check motor power against unit power.
Contact your local ABB representative.
Contact your local ABB representative.
Check input power line fuses.
Check for input power supply imbalance.
Check fault function parameter setting.
Contact your local ABB representative.
Contact your local ABB representative.
Check input power connections.
Check fault function parameter setting.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check parameter settings. Following must apply:
2007
< 2008,
2007/9907
and
2008/9907
Check parameter group
13 ANALOG INPUTS
settings. Following must apply:
1301
< 1302.
109
Motor
are within range.
Fault tracing