Control Connections; Brake Resistor Connection; Efficiency; Cooling - ABB ACS150 User Manual

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

120

Control connections

Analog input GND
Auxiliary voltage +24V
Digital inputs DI1...DI5
(frequency input DI5)
Relay output COM, NC, NO
Wire size
Torque

Brake resistor connection

Short-circuit protection
(IEC 61800-5-1, IEC 60439-1,
UL 508C)

Efficiency

Cooling

Method
Free space around the drive See chapter

Degrees of protection

Technical data
Voltage signal, unipolar
Current signal, unipolar
Potentiometer reference value (+10V)
Resolution
Accuracy
Voltage
Type
Frequency input
Input impedance
Type
Max. switching voltage
Max. switching current
Max. continuous current
Relay connections
I/O connections
Relay connections
I/O connections
The brake resistor output is conditionally short-circuit proof by IEC/EN 61800-5-1 and
UL 508C. For correct fuse selection, contact your local ABB representative. Rated
conditional short-circuit current as defined in IEC 60439-1 and the Short-circuit test current
by UL 508C is 100 kA.
Approximately 95 to 98% at nominal power level, depending on the drive size and options
R0: Natural convection cooling. R1...R2: Internal fan, flow direction from bottom to top.
Mechanical
installation, page 21.
IP20 (cabinet installation) / UL open: Standard enclosure. The drive must be installed in a
cabinet to fulfil the requirements for shielding from contact.
IP20 / NEMA 1: Achieved with an option kit including a hood and a connection box.
0 (2)...10 V, R
> 312 kohm
in
0 (4)...20 mA, R
= 100 ohm
in
10 V ± 1%, max. 10 mA, R < 10 kohm
0.1%
±1%
24 VDC ± 10%, max. 200 mA
12...24 VDC with internal or external supply
PNP and NPN
Pulse train 0...16 kHz (DI5 only)
2.4 kohm
NO + NC
250 VAC / 30 VDC
0.5 A / 30 VDC; 5 A / 230 VAC
2 A rms
2
1.5...0.20 mm
16...24 AWG
2
1... 0.14mm
16...26 AWG
0.5 N·m / 4.4 lbf in.
0.22 N·m / 2 lbf in.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs350

Table of Contents