ABB ACS150 User Manual page 15

0.37...4 kw, 0.5...5 hp
Table of Contents

Advertisement

Pressure boost pump
The figure below shows an application example: The controller adjusts the speed of
a pressure boost pump according to the measured pressure and the set pressure
reference.
Example:
Pressure boost pump
A C S 6 0 0
ACS150
A C T
P A R
F U N C
D R I V E
E N T E R
L O C
R E S E T
R E F
R E M
3
2
3
How to scale the PID actual (feedback) signal 0...10 bar / 4...20 mA
PID feedback is connected to AI1 and
1. Set
9902
APPLICATION MACRO to 6 (PID CONTROL). Check scaling: 1301
MINIMUM AI1 as default 20% and 1302 MAXIMUM AI1 as default 100%. Check
that
1106
REF2 SELECT is set to 19 (PID1OUT).
2. Set
3408
SIGNAL2 PARAM to 130 (PID1 FBK).
3. Set 3409 SIGNAL2 MIN to 0.
4. Set 2310 SIGNAL2 MAX to 10.
5. Set 3411 OUTPUT2 DSP FORM to 9 (DIRECT).
6. Set 3412 OUTPUT2 UNIT to 0 (NO UNIT).
7. Set
4006
UNITS to 0 (NO UNIT).
8. Set
4007
UNIT SCALE to 1.
9. Set
4008
0% VALUE to 0.
10. Set
4009
100% VALUE to 10.
How to scale the PID setpoint signal
1. Set
4010
SET POINT SEL to 19 (INTERNAL).
2. Set
4011
INTERNAL SETPNT to 5.0 ("bar" is not displayed on the drive control
panel) as an example.
For detailed parameter descriptions, see the related parameters in ACS150 user's
manual (3AFE68576032 [EN]).
PID control block diagram
%ref
Actual values
4014
.
0...10 bar
. .
0 . . . 1 0 b a r
4...20 mA
4021
4 . . . 2 0 m A
AI1
AI2
IMOT
4001
4002
4003
4004
4005
PIDmax
PIDmin
...
4016
ACT1 INPUT is set to AI1.
PID
ref
k
ti
td
Frequency
i
reference
dFiltT
errVInv
oh1
ol1
%ref =
4010
Update notice
13