60
3-wire macro
This macro is used when the drive is controlled using momentary push-buttons. It
provides three constant speeds. To enable the macro, set the value of parameter
9902
For the parameter default values, see section
macros
see section
Note: When the stop input (DI2) is deactivated (no input), the control panel start and
stop buttons are disabled.
Default I/O connections
1...10 kohm
Alternative connection
for AI1. If used, switch
IU selector to U
(0...10 V voltage
signal).
1)
See parameter group
DI3 DI4 Operation (parameter)
0
1
0
1
Application macros
to 2 (3-WIRE).
on page 65. If you use other than the default connections presented below,
I/O terminals
on page 34.
I/O connection
SCR
AI
GND
2)
+10V
+24V
GND
DCOM
DI1
DI2
DI3
DI4
DI5
Relay connection
COM
NC
NO
12 CONSTANT
0 Set speed through
integrated potentiometer
0 Speed 1 (1202)
1 Speed 2 (1203)
1 Speed 3 (1204)
Default parameter values with different
3)
Signal cable shield (screen)
Frequency reference: 0...20 mA
Analog input circuit common
Reference voltage: +10 VDC, max. 10 mA
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Start (pulse
)
Stop (pulse
)
Forward (0) / Reverse (1)
Constant speed selection
Constant speed selection
4)
Relay output
No fault [Fault (-1)]
2)
SPEEDS:
360 degree grounding under a clamp.
3)
Tightening torque = 0.22 N·m / 2 lbf. in.
4)
Tightening torque = 0.5 N·m / 4.4 lbf. in.
1)