Parameters in the Long Parameter mode
Index Name/Selection

12 CONSTANT SPEEDS

1201
CONST SPEED SEL
0 = NOT SEL
1 = DI1
2 = DI2
3 = DI3
4 = DI4
5 = DI5
7 = DI1,2
8 = DI2,3
9 = DI3,4
10 = DI4,5
12 = DI1,2,3
13 = DI3,4,5
-1 = DI1(INV)
-2 = DI2(INV)
-3 = DI3(INV)
-4 = DI4(INV)
Description
Constant speed selection and values.
It is possible to define seven positive constant speeds. Constant speeds are
selected with digital inputs. Constant speed activation overrides the external
speed reference. Constant speed selections are ignored if drive is in local
control mode.
Selects the constant speed activation signal.
No constant speed in use
Speed defined by parameter
digital input DI1. 1 = active, 0 = inactive.
Speed defined by parameter
digital input DI2. 1 = active, 0 = inactive.
Speed defined by parameter
digital input DI3. 1 = active, 0 = inactive.
Speed defined by parameter
digital input DI4. 1 = active, 0 = inactive.
Speed defined by parameter
digital input DI5. 1 = active, 0 = inactive.
Constant speed selection through digital inputs DI1 and DI2.1 = DI active,
0 = DI inactive.
DI1 DI2 Operation
0
0
No constant speed
1
0
Speed defined by parameter
0
1
Speed defined by parameter
1
1
Speed defined by parameter
See selection DI1,2.
See selection DI1,2.
See selection DI1,2.
Constant speed selection through digital inputs DI1, DI2 and DI3.
1 = DI active, 0 = DI inactive.
DI1 DI2
DI3 Operation
0
0
0
No constant speed
1
0
0
Speed defined by parameter
0
1
0
Speed defined by parameter
1
1
0
Speed defined by parameter
0
0
1
Speed defined by parameter
1
0
1
Speed defined by parameter
0
1
1
Speed defined by parameter
1
1
1
Speed defined by parameter
See selection DI1,2,3.
Speed defined by parameter
inverted digital input DI1. 0 = active, 1 = inactive.
Speed defined by parameter
inverted digital input DI2. 0 = active, 1 = inactive.
Speed defined by parameter
inverted digital input DI3. 0 = active, 1 = inactive.
Speed defined by parameter
inverted digital input DI4. 0 = active, 1 = inactive.
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1
1203
CONST SPEED 2
1204
CONST SPEED 3
1202
CONST SPEED 1
1203
CONST SPEED 2
1204
CONST SPEED 3
1205
CONST SPEED 4
1206
CONST SPEED 5
1207
CONST SPEED 6
1208
CONST SPEED 7
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1 is activated through
1202
CONST SPEED 1 is activated through
Def
9 = DI3,4
Actual signals and parameters
77