Parameters in the Long Parameter mode
Index Name/Selection
1 = FORWARD
2 = REVERSE
3 = REQUEST
1010
JOGGING SEL
1 = DI1
2 = DI2
Description
Fixed to forward
Fixed to reverse
Direction of rotation control allowed
Defines the signal that activates the jogging function. The jogging function is
typically used to control a cyclical movement of a machine section. One push
button controls the drive through the whole cycle: When it is on, the drive
starts, accelerates to a preset speed at a preset rate. When it is off, the drive
decelerates to zero speed at a preset rate.
The figure below describes the operation of the drive. It also represent how
the drive shifts to normal operation (= jogging inactive) when the drive start
command is switched on. Jog cmd = state of the jogging input, Start cmd =
state of the drive start command.
Speed
1 2
Phase Jog
Start
Description
cmd
cmd
1-2
1
0
Drive accelerates to the jogging speed along the
acceleration ramp of the jogging function.
2-3
1
0
Drive runs at the jogging speed.
3-4
0
0
Drive decelerates to zero speed along the deceleration
ramp of the jogging function.
4-5
0
0
Drive is stopped.
5-6
1
0
Drive accelerates to the jogging speed along the
acceleration ramp of the jogging function.
6-7
1
0
Drive runs at the jogging speed.
7-8
x
1
Normal operation overrides the jogging. Drive
accelerates to the speed reference along the active
acceleration ramp.
8-9
x
1
Normal operation overrides the jogging. Drive follows
the speed reference.
9-10
0
0
Drive decelerates to zero speed along the active
deceleration ramp.
10-
0
0
Drive is stopped.
x = State can be either 1 or 0.
Note: The jogging is not operational when the drive start command is on.
Note: The jogging speed overrides the constant speeds
SPEEDS).
Note: The ramp shape time
during jogging (i.e. linear ramp).
Jogging speed is defined by parameter
and deceleration times are defined by parameters
and
2206
DECERLER TIME 2. See also parameter
DELAY.
Digital input DI1. 0 = jogging inactive, 1 = jogging active.
See selection DI1.
3 4 5
6
7
8 9
(2207
RAMP SHAPE 2) must be set to zero
1208
CONST SPEED 7, acceleration
2205
2112
Def
0 = NOT SEL
t
10
(12 CONSTANT
ACCELER TIME 2
ZERO SPEED
Actual signals and parameters