VALUES (B) AND (C) CAN BE INVERTED DEPENDING ON THE POSITION OF THE COMBUSTIBLE WALL.
VALUE (C) MEETS THE MINIMUM STANDARD REQUIREMENTS TO PERFORM MAINTENANCE SAFELY.
HOWEVER, WE RECOMMEND A 30" CLEARANCE TO FACILITATE MAINTENANCE OR REPLACEMENT
OF CERTAIN PARTS.

5.4.1 FLOOR PROTECTION

If the floor is made of non-combustible material,
-
no floor protector is required.
-
If the floor is made of combustible material, a non-
combustible material floor protector is required
(see table below).
A
B
C
D
E
*Steel with a minimum thickness of 0.015" (0.38 mm) or ceramic tiles sealed together with grout. No protection is
required if the unit is installed on a non-combustible floor (ex: concrete).
Note 1: The floor protection at the back of the furnace is limited to the furnace's required clearance (A) if such
clearance is smaller than 8 inches (203 mm).
Note 2: Only required under the horizontal section of the connector. Must exceed each side of the connector
pipe by at least 2 inches (51 mm).
FLOOR PROTECTION*
CANADA
18" (457 mm)
From door opening
N/A (USA only)
8" (203 mm)
8" (203 mm) – Note 1
N/A (USA only)
USA
16" (406 mm)
From door opening
8" (203 mm)
From door opening
N/A (Canada only)
N/A (Canada only)
Note 2