Omron E5CC User Manual page 210

Digital
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

6 Parameters
al-1
al-2
al-3
al-4
This parameter is set to one of the input values "X" in the alarm type list. (Page 3-15)
• These parameters set the alarm values for alarms 1 to 4.
• During temperature input, the decimal point position depends on the currently selected
sensor, and during analog input it depends on the Decimal Point parameter setting.
Function
Alarms Other Than an MV Alarm
MV Alarms
Related Parameters
See
See
Input Type (Initial Setting Level): Page 6-42
Scaling Upper Limit (Initial Setting Level): Page 6-43
Scaling Lower Limit (Initial Setting Level): Page 6-43
Decimal Point (Initial Setting Level): Page 6-43
Alarm 1 to 4 Type (Initial Setting Level): Page 6-47
Alarm 1 to 4 Hysteresis (Initial Setting Level): Page 6-51
Standby Sequence Reset (Advanced Function Setting Level): Page 6-62
Auxiliary Output 1 to 4 Open in Alarm (Advanced Function Setting Level): Page 6-63
Alarm 1 to 4 Latch (Advanced Function Setting Level): Page 6-68
6 - 14
Alarm Value 1
Alarm Value 2
Alarm Value 3
Alarm Value 4
Setting range
−1999 to 9999
Setting range
−199.9 to 999.9
Alarm 1 to alarm 4 must be assigned.
The Alarm 1 to 4 Type parameters must not be set
to 0, 1, 4, 5, or 12.
Unit
Default
EU
0
Unit
Default
%
0.0
E5@C Digital Temperature Controllers User's Manual (H174)