5 Advanced Operations

5-20 Using a Remote SP

A remote SP uses a remote SP input that is scaled between the remote SP upper and lower limits as
the SP. (The remote SP can be 4 to 20 mA DC, 0 to 20 mA DC, 1 to 5 VDC, 0 to 5 VDC, or 0 to 10
VDC.) Set the Remote SP Enable parameter (Advanced Function Setting Level) to ON and select a
remote SP in the SP Mode parameter (Adjustment Level) to enable using a remote SP. You can also
use an event input to switch to SP Mode.
Parameter
Remote SP Enable (rspu)
Remote SP Input (rs-t)
Remote SP Upper Limit (rsph)
Remote SP Lower Limit (rspl)
SP Tracking (sptr)
SP Mode (spmd)
Remote SP Monitor (rsp)
Remote SP Input Shift (rss)
Remote SP Input Slope Coefficient
(rsrt)
Precautions for Correct Use
• When the ST (self-tuning) parameter is turned ON, the SP Mode parameter is forcibly set to
LSP.
• The remote SP input is not accepted during autotuning. Autotuning is executed for the remote
SP at the beginning of autotuning.
• Changes in the remote SP value are not used as conditions for resetting the standby
sequence.
Remote SP Scaling
• You can scale the remote SP input for the PV input range with the remote SP upper and lower
limits.
• The remote SP input can be from the remote SP lower limit −10% to the remote SP upper limit
+10%. Input values outside of this range are treated as out-of-range input values (RSP input
errors) and clamped to the upper or lower limit. The RSP indicator will flash in Remote SP Mode.
Also, the Remote SP Monitor will flash on the No. 2 display in any SP Mode.
• When you use the remote SP input value as the control SP, it is restricted by the set point upper
limit and the set point lower limit.
5 - 56
Setting range
OFF: Disable, ON: Enable
4 to 20 mA DC, 0 to 20 mA DC, 1 to 5
VDC, 0 to 5 VDC, or 0 to 10 VDC
Temperature input: Input setting
range lower limit to Input setting
range upper limit
Analog input: Scaling lower limit to
Scaling upper limit
OFF: Disable, ON: Enable
LSP: Local SP, RSP: Remote SP
Remote SP lower limit −10% to
Remote SP upper limit +10%
Temperature input: −199.9 to 999.9
Analog input: −1,999 to 9,999
0.001 to 9.999
Unit
Default
None
OFF
---
4 to 20 mA
DC
EU
1300
−200
EU
None
OFF
None
LSP
EU
---
°C or °F
0.0
EU
0
EU
1.000
E5@C Digital Temperature Controllers User's Manual (H174)
Level
Advanced Function
Setting Level
Advanced Function
Setting Level
Advanced Function
Setting Level
Advanced Function
Setting Level
Advanced Function
Setting Level
Adjustment Level
Adjustment Level
Adjustment Level
Adjustment Level