The alarm 1, 2, 3, or 4 output is prevented from turning OFF until after the delay times set in these
parameters have elapsed.
• Set the time for which the OFF delay is to be enabled.
• To disable the OFF delay, set 0.
Function
Setting
Related Parameters
See
See
Alarm 1 to 4 Type (Initial Setting Level): Page 6-47
mVse
• This parameter sets whether or not the MV at Stop and MV at PV Error parameters are to
be displayed.
Function
Setting
Related Parameters
See
See
MV at Stop (Adjustment Level): Page 6-32
MV at PV Error (Adjustment Level): Page 6-33
E5@C Digital Temperature Controllers User's Manual (H174)
Alarm 1 OFF Delay
Alarm 2 OFF Delay
Alarm 3 OFF Delay
Alarm 4 OFF Delay
Setting range
0 to 999
MV at Stop and Error Addition
000
Setting range
on: Displayed, off: Not displayed
Alarm 1 must be assigned, and the alarm 1 type
must not be 0, 12, or 13.
Alarm 2 must be assigned, and the alarm 2 type
must not be 0, 12, or 13.
Alarm 3 must be assigned, and the alarm 3 type
must not be 0, 12, or 13.
Alarm 4 must be assigned, and the alarm 4 type
must not be 0, 12, or 13.
Unit
Default
Seconds
0
Control must be set to 2-PID control.
Default
off