4 Basic Operation
Example 3 (E5EC/E5AC Position-proportional Models Only)
Setup Procedure
Power ON
Initial Setting Level
Set input
specifications
Set control
specifications
Set travel time.
Operation Level
Set SP
Adjustment Level
Set SP ramp
Start operation
4 - 10
Input type:
5 (K thermocouple, −200°C to 1,300°C)
Control method:
Floating control
SP ramp time unit: EU/min
Travel time:
45 s
SP ramp set value: 10 EU (°C)
Set point:
250°C
Power ON
An s.err error will be
displayed if the power
supply is turned ON
before the sensor is
connected.
Operation Level
25
PV/SP
0
Press the O Key for at least 3 s.
Control stops.
Initial Setting Level
in-t
Check input type.
Input Type:
5
M
Floating control:
Check that control
cl f l
method is floating
f l o t
control.
Close control:
M
Use the U and D
mo t
Keys to set the
Travel Time:
45
travel time to 45 s.
Press the O Key for at least 1 s.
Control starts.
Operation Level
Use the U and D
25
PV/SP:
Keys to set the SP
250
to 250°C.
Press the O Key (for less than 1 s).
Adjustment Level
at
off
M
Use the U and D
sprt
Keys to set the SP
SP Ramp Set
10
Value:
ramp set value to
10°C.
Press the O Key (for less than 1 s).
Operation Level
25
PV/SP:
250
M
Confirm that
Running:
r-5
control is running.
Stopped:
run
M
Start operation.
E5@C Digital Temperature Controllers User's Manual (H174)
5
flot
clo5
45
250
10
250
run
stop