Advertisement

Parameters
Characters
out1
Control Output 1
Assignment
out2
Control Output 2
Assignment
E5@C Digital Temperature Controllers User's Manual (H174)
Setting (monitor) value
Relay Output or Voltage Output (for Driving SSR)
NONE: No assignment
O: Control output (heating)
C-O: Control output (cooling)
ALM1: Alarm 1
ALM2: Alarm 2
ALM3: Alarm 3
ALM4: Alarm 4
HA: Heater alarm (HB + HS)
HB: Heater burnout alarm (HB)
HS: Heater short alarm (HS)
S.ERR: Input error
RS.ER: Remote SP input error
*3
P.END: Program End output
RUN: RUN output
ALM: Integrated alarm
*4
WR1: Work bit 1
*4
WR2: Work bit 2
*4
WR3: Work bit 3
*4
WR4: Work bit 4
*4
WR5: Work bit 5
*4
WR6: Work bit 6
*4
WR7: Work bit 7
*4
WR8: Work bit 8
*2
Current Output
NONE: Not assigned.
O: Control output (heating)
C-O: Control output (cooling)
Same as the Control Output 1 Assignment
parameter.
A Appendices
Display
Default
*2
O
none
o
c-o
alm1
alm2
alm3
alm4
ha
hb
hs
s.err
rs.er
p.end
run
alm
wr1
wr2
wr3
wr4
wr5
wr6
wr7
wr8
none
o
c-o
Same as the
NONE
Control
Output 1
Assignment
parameter.
Unit
None
None
A
A - 25