Setting
Event input
Event input
Controlling the Start of the Simple Program Function
When the Event Input Assignment parameter is set to PRST (program start), the program will start
when the event input turns ON. The program will be reset when the input turns OFF and the
RUN/STOP status will automatically switch to STOP mode. If the program END output is ON, the
program END output will turn OFF.
Setting
Event input
Event input
Control by Inverting Direct/Reverse Operation
When the Event Input Assignment parameter is set to DRS (Invert Direct/Reverse Operation) and
the Direct/Reverse Operation parameter is set for reverse operation, control starts with direct
operation (cooling control) when the event input turns ON and control starts with reverse operation
(heating control) when the event input turns OFF.
Setting
Event input
Event input
Switching the SP Mode
When the Event Input Assignment parameter is set to RSP (SP mode switch), operation with a
remote SP will start when the event input turns ON. Operation with a local SP will start when the
event input turns OFF. The RSP operation indicator will light during Remote SP Mode.
Setting
Event input
Event input
Switching 100% AT Execute/Cancel
When the Event Input Assignment parameter is set to AT-2 (100% AT Execute/Cancel), 100% AT will
be executed when the event input turns ON and will be cancelled when the input turns OFF.
Setting
Event input
Event input
Switching 40% AT Execute/Cancel
When the Event Input Assignment parameter is set to AT-1 (40% AT Execute/Cancel), 40% AT will
be executed when the event input turns ON and will be cancelled when the input turns OFF.
Setting
Event input
Event input
E5@C Digital Temperature Controllers User's Manual (H174)
Input contact
Status
OFF
Automatic
ON
Manual
Input contact
Status
OFF
Reset
ON
Start
Direct/Reverse
Input contact
Operation parameter
OFF
Direct operation (cooling)
Reverse operation
(heating)
ON
Direct operation (cooling)
Reverse operation
(heating)
Input contact
Status
OFF
Local SP
ON
Remote SP
Input contact
Status
OFF
100% AT cancelled
ON
100% AT executed
Input contact
Status
OFF
40% AT cancelled
ON
40% AT executed
5 Advanced Operations
000
Status
Direct operation (cooling)
Reverse operation
(heating)
Reverse operation
(heating)
Direct operation (cooling)
5 - 13