A-6-3 Initial Setting Level - Omron E5CC User Manual

Digital
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

A Appendices
A-6-3
Initial Setting Level
Parameters
Characters
in-t
Input Type
in-h
Scaling Upper Limit
in-l
Scaling Lower Limit
dp
Decimal Point
d-u
Temperature Unit
sl-h
SP Upper Limit
sl-l
SP Lower Limit
cntl
PID ON/OFF
s-hc
Standard or
Heating/Cooling
st
ST
ptrn
Program Pattern
000
cp
Control Period
(Heating)
c-cp
Control Period
(Cooling)
orev
Direct/Reverse
Operation
A - 20
Setting (monitor) value
Temperature
0: Pt100
input
1: Pt100
2: Pt100
3: JPt100
4: JPt100
5: K
6: K
7: J
8: J
9: T
10: T
11: E
12: L
13: U
14: U
15: N
16: R
17: S
18: B
19: W
20: PLII
21: 10 to 70°C
22: 60 to 120°C
23: 115 to 165°C
24: 140 to 260°C
Analog input
25: 4 to 20 mA
26: 0 to 20 mA
27: 1 to 5 V
28: 0 to 5 V
29: 0 to 10 V
Scaling lower limit + 1 to 9,999
−1,999 to scaling upper limit −1
0 to 3
°C, °F
Temperature input: SP lower limit + 1 to Input setting
range upper limit
Analog input: SP lower limit + 1 to scaling upper limit
Temperature input: Input setting range lower limit to
SP upper limit − 1
Analog input: Scaling lower limit to SP upper limit − 1
ON/OFF 2-PID
Standard or heating/cooling
OFF, ON
OFF, STOP, CONT
0.1, 0.2, 0.5, or 1 to 99
0.1, 0.2, 0.5, or 1 to 99
Reverse operation, direct operation
Display
Default
5
5
100
0
0
°C
c
f
,
1300
100
−200
0
onof, pid
ON/OFF
stnd, h-c
Standard
off, on
ON
off, stop,
OFF
cont
0.1, 0.2, 0.5, 1
Relay
to 99
output: 20
Voltage
output (for
driving
SSR): 2
0.1, 0.2, 0.5, 1
Relay
to 99
output: 20
Voltage
output (for
driving
SSR): 2
or-r, or-d
Reverse
operation
E5@C Digital Temperature Controllers User's Manual (H174)
Unit
None
None
None
None
None
None
EU
EU
None
None
None
None
Seconds
Seconds
None