6 Parameters
rsph
rspl
You can scale the remote SP input for the PV input range with the values that are set for the
Remote SP Upper and Lower Limit parameters.
Function
Remote SP Input of 4 to 20 mA
Remote SP Upper Limit +10%
Remote SP Upper Limit
Remote SP Lower Limit
Remote SP Lower Limit −10%
• The remote SP input can be from the remote SP lower limit −10% to the remote SP upper
limit +10%. Input values outside of this range are treated as out-of-range input values
(RSP input errors) and clamped to the upper or lower limit. The RSP indicator will flash in
Remote SP Mode. Also, the Remote SP Monitor will flash on the No. 2 display in any SP
Mode.
• When you use the remote SP input value as the control SP, it is restricted by the set point
upper limit and the set point lower limit.
Remote SP Upper Limit
Setting
Remote SP Lower Limit
Related Parameters
See
See
Remote SP Input (Advanced Function Setting Level): Page 6-81
Remote SP Enable (Advanced Function Setting Level): Page 6-81
6 - 82
000
Remote SP Upper Limit
000
Remote SP Lower Limit
RSP
Parameter
Temperature input: Input setting range lower
limit to Input setting range upper limit
Analog input: Scaling lower limit to Scaling
upper limit
There must be a remote SP input.
The ST parameter must be set to OFF.
The Remote SP Enable parameter must be set to
ON.
4.0
20.0
2.4(−10%)
21.6(110%)
Setting range
E5@C Digital Temperature Controllers User's Manual (H174)
Input (mA)
Unit
Default
1300
EU
−200