Omron E5CC User Manual page 72

Digital
Hide thumbs Also See for E5CC:
Table of Contents

Advertisement

3 Part Names and Basic Procedures
List of Input Types
Input type
Resistance
thermometer
Thermocouple
Infrared temperature
sensor ES1B
Current input
Voltage input
*
The default is 5.
3 - 12
Specifications
Set value
Pt100
0
1
2
JPt100
3
4
K
5*
6
J
7
8
T
9
10
E
11
L
12
U
13
14
N
15
R
16
S
17
B
18
W
19
PLII
20
10 to 70°C
21
60 to 120°C
22
115 to 165°C
23
140 to 260°C
24
4 to 20 mA
25
0 to 20 mA
26
1 to 5 V
27
0 to 5 V
28
0 to 10 V
29
Temperature range in °C
−200 to 850
−199.9 to 500.0
0.0 to 100.0
−199.9 to 500.0
0.0 to 100.0
−200 to 1300
−20.0 to 500.0
−100 to 850
−20.0 to 400.0
−200 to 400
−199.9 to 400.0
−200 to 600
−100 to 850
−200 to 400
−199.9 to 400.0
−200 to 1300
0 to 1700
0 to 1700
100 to 1800
0 to 2300
0 to 1300
0 to 90
0 to 120
0 to 165
0 to 260
One of the following ranges according to the scaling:
−1999 to 9999
−199.9 to 999.9
−19.99 to 99.99
−1.999 to 9.999
E5@C Digital Temperature Controllers User's Manual (H174)
Temperature range in °F
−300 to 1500
−199.9 to 900.0
0.0 to 210.0
−199.9 to 900.0
0.0 to 210.0
−300 to 2300
0.0 to 900.0
−100 to 1500
0.0 to 750.0
−300 to 700
−199.9 to 700.0
−300 to 1100
−100 to 1500
−300 to 700
−199.9 to 700.0
−300 to 2300
0 to 3000
0 to 3000
300 to 3200
0 to 3200
0 to 2300
0 to 190
0 to 240
0 to 320
0 to 500

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5acE5ec

Table of Contents