6 Parameters
lcr2
This parameter measures the heater current from the CT input used for detecting SSR short-circuits.
This parameter measures and displays the heater current value.
• The HS alarm is not detected if the OFF time for the control output for heating is 100 ms
or less (35 ms or less if the control period is 0.1 or 0.2 s).
Function
Monitor
• ffff is displayed when 55.0 A is exceeded.
• If an alarm is output for the HS Alarm 2 parameter, the No. 1 display will flash the
Leakage Current 2 Monitor parameter.
Related Parameters
See
See
HS Alarm 1 (Adjustment Level): Page 6-24
HS Alarm 2 (Adjustment Level): Page 6-25
HS Alarm Use (Advanced Function Setting Level): Page 6-74
Error Display lcr2: Page A-12
prst
This parameter starts and stops the simple program function.
• The RUN/STOP status will automatically switch to RUN when this parameter is set to
STRT.
• The simple program will stop when this parameter is set to RSET.
Function
• This parameter will function as a monitor display for the start/stop status of the simple
program if an event input is selected to start the simple program.
RSET
Operation
STRT
Related Parameters
See
See
Soak Time Remain (Operation Level): Page 6-13
RUN/STOP (Operation Level): Page 6-13
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Program Pattern (Initial Setting Level): Page 6-46
Soak Time Unit (Advanced Function Setting Level): Page 6-80
6 - 12
Leakage Current 2 Monitor
Monitor range
0.0 to 55.0
000
Program Start
Setting range
Stops the simpler program.
Starts the simpler program.
HB and HS alarms must be supported (two CTs).
000
The HS Alarm Use parameter must be set to ON.
Unit
A
The Program Pattern parameter must not be set to
OFF.
E5@C Digital Temperature Controllers User's Manual (H174)