Parameters — Technical functions and
Parameter no.
600
Operating hours
601
Hours run
602
kWh counter
603
No. of cut-ins
604
No. of overtemps
605
No. of overvoltages
Function:
These parameters can be read out via the
serial communication port and via the display
in the parameters.
Description of choice:
Operating hours, parameter 600:
Indicates the number of hours in which the frequency
converter has been in operation.
The value is updated in the frequency converter every
hour and saved when the unit is turned off.
Hours run, parameter 601:
Indicates the number of hours in which the
frequency converter has been in operation since
reset in parameter 619.
The value is updated in the frequency converter every
hour and saved when the unit is turned off.
Parameter no.
606
Digital inputs
607
Control word
608
Status word
609
Reference
610
Feedback
611
Output frequency
612
Output voltage
613
Output current
614
DC link voltage
Function:
Via this parameter it is possible to see up to 20
data-logs, where [0] is the latest log and [19] the
oldest. Each data-log is made every 160 ms as long
as a start signal has been given. If a stop signal is
given, the latest 20 data-logs will be saved and the
values will be available on the display. This is useful,
e.g. when carrying out service after a trip.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.R3.02 -
Description
Operating data
(OPERATING
HOURS)
(RUNNING HOURS)
(KWH COUNTER)
(POWER UP's)
(OVER TEMP's)
(OVER VOLT'S)
Description
Data log
(LOG: DIGITAL INP)
(LOG: CONTROL
WORD
(LOG: BUS STAT WD)
(LOG: REFERENCE)
(LOG: FEEDBACK)
(LOG: MOTOR
FREQ.)
(LOG: MOTOR VOLT)
(LOG: MOTOR
CURR.)
(LOG: DC LINK VOLT)
AKD 5000
Display text
Hours
Hours
kWh counter, parameter 602:
States the power consumption from mains in
kWh as a mean value over one hour. Reset
counter: Parameter 618.
No. of cut-ins, parameter 603:
States the number of power-ups of the supply
voltage to the frequency converter.
No. of overtemps, parameter 604:
States the number of temperature faults there has
been on the frequency converter.
No. of overvoltages, parameter 605:
States the number of overvoltages there has
been on the frequency converter.
Display text
Decimal
Decimal
Decimal
Par. 416
This parameter can be read out via the serial
communication port or via the display.
Description of choice:
The data-log number is stated in square brackets: [1].
Data-logs are frozen if there is a trip and released when
the frequency converter is subsequently reset.
Data-logging is active while the motor is running.
Unit
Range
0 - 130,000.0
0 - 130,000.0
kWh
0 - 9999
Nos.
0 - 9999
Nos.
0 - 9999
Nos.
0 - 9999
Unit
Range
0 - 255
0 - 65535
0 - 65535
%
0 - 100
999,999.99 -
999,999.99
Hz.
0.0 - 999.9
Volt
50 - 1000
Amp
0.0 - 999.9
Volt
0.0 - 999.9