Application configuration

Using this parameter enables the choice of a
configuration (setting) of the frequency converter
that fits the application in which the frequency
converter is to be active.
NB!:
First, the motor nameplate date must be
set in parameters 102-106.

Setting of parameters

Select Speed control, open loop if a normal
speed adjustment without external feedback
S S S S p p p p e e e e e e e e d d d d c c c c o o o o n n n n t t t t r r r r o o o o l l l l , , , , o o o o p p p p e e e e n n n n l l l l o o o o o o o o p p p p : : : :
Parame-
ter:
100
Configuration
200
Output frequency range/direction
201
Output frequency low limit
202
Output frequency high limit
203
Reference/feedback range
204
Minimum reference
205
Maximum reference
Select Process control, closed loop if the application
has a feedback signal that is not directly related to
motor speed (rpm/Hz), but some other unit, such
P P P P r r r r o o o o c c c c e e e e s s s s s s s s c c c c o o o o n n n n t t t t r r r r o o o o l l l l , , , , c c c c l l l l o o o o s s s s e e e e d d d d l l l l o o o o o o o o p p p p ( ( ( ( P P P P r r r r o o o o c c c c e e e e s s s s s s s s P P P P I I I I D D D D ) ) ) ) : : : :
Parame-
ter:
100
Configuration
200
Output frequency range/direction
201
Output frequency low limit
202
Output frequency high limit
203
Reference/feedback range
414
Minimum feedback
415
Maximum feedback
204
Minimum reference
205
Maximum reference
416
Process units
437
Process PID normal/inverse
439
Process PID start frequency
440
Process PID proportional gain
441
Process PID integration time
444
Process PID lowpass filter
MG.50.R3.02 -
AKD 5000
There is a choice of the following configurations:
- Speed control, open loop
- Speed control, closed loop
- Process control, closed loop
- Torque control, open loop
- Torque control, speed feedback
The selection of special motor characteristics can be
combined with any application configuration.
signals is required (the internal slip compensation
is operating) from motor or unit.
Set the following parameters in order shown:
Setting:
Speed control, open loop
Only if [0] or [2] in par. 200
Only if [0] in par. 203
as temperature, pressure, etc. Set the following
parameters in the order shown:
Setting:
Process control, closed loop
Only if [0] or [2] in par. 200
Only if [0] in par. 203
Data value:
[0]
Data value:
[3]
51