Free a data-log if there is a trip and release it when
resetting the frequency converter. Data-logging
is active when the motor is running.
Digital inputs, parameter 606:
The value for the digital inputs is given as a decimal
figure within the range of 0-255.
The data-log number is stated in square brackets: [1]
EXT. REFERENCE, %
63.0 %
606 DATALOG:DIGITALINPUT
[0] 40
Control word, parameter 607:
The value for the control word is given as a decimal
figure within the range of 0-65535.
Status word, parameter 608:
The value for the bus status word is given as a
decimal figure within the range of 0-65535.
Reference, parameter 609:
The value of the reference is stated as a %
in the interval 0 - 100%.
Feedback, parameter 610:
The value is stated as the parameterised feedback.
Output frequency, parameter 611:
The value of the motor frequency is stated as a
frequency in the interval 0.0 - 999.9 Hz.
Output voltage, parameter 612:
The value of the motor voltage is stated as Volts
in the interval 50 - 1000 V.
Output current, parameter 613:
The value for the motor current is stated as Amps
in the interval 0.0 - 999.9 A.
DC link voltage, parameter 614:
The value of the DC link voltage is stated as
Volts in the interval 0.0 - 999.9 V.
615 Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index 1 - 10]
Function:
This parameter makes it possible to see the
reason why a trip occurs.
= factory setting. () = display text [] = value for use in communication via serial communication port
98
AKD 5000
10 (0-10) log values are stored.
The lowest log number (1) contains the latest/most
recently saved data value; the highest log number
(10) contains the oldest data value.
Description of choice:
Given as a number code, in which the trip
number refers to an alarm code that can be seen
from the table on page 143.
Reset the fault log after manual initialisation.
616 Fault log: Time
Value:
[Index 1 - 10]
Function:
This parameter makes it possible to see the total
number of operating hours before the trip occurred.
10 (0-10) log values are stored.
The lowest log number [1] contains the latest/most
recently saved data value, while the highest log
number [10] contains the oldest data value.
Description of choice:
Read out as an option.
Indication range: 0.0 - 9999.9.
Reset the fault log after manual initialisation.
617 Fault log: Value
Value:
[Index 1 - 10]
Function:
This parameter makes it possible to see at what
current or voltage a given trip occurred.
Description of choice:
Read out as one value.
Indication range: 0.0 - 999.9.
Reset the fault log after manual initialisation.
618 Reset of kWh counter
Value:
Error code 0 - 44
No reset (DO NOT RESET)
Reset (RESET COUNTER)
(F.LOG: TIME)
(F.LOG: VALUE)
(RESET KWH COUNT)
[0]
[1]
MG.50.R3.02 -