Akd 5000 series, electronic controls, refrigeration and air conditioning controls, adap-kool refrigeration control systems
Table of Contents

Advertisement

Operation and Display

001 Language
(LANGUAGE)
Value:
English (ENGLISH)
German (DEUTSCH)
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPAÑOL)
Italian (ITALIANO)
Function:
The choice in this parameter defines the language
to be used on the display.
Description of choice:
There is a choice of English [0], German [1], French
[2], Danish [3], Spanish [4] and Italian [5].
002 Local/remote control
(OPERATION SITE)
Value:
Remote control (REMOTE)
Local control (LOCAL)
Function:
There is a choice of two methods of controlling
the frequency converter.
Description of choice:
If Remote control [0] is selected, the frequency
converter can be controlled via:
1. The control terminals or the serial
communication port.
2. The [START] key. However, this cannot overrule
Stop commands (also start-disable) entered via the
digital inputs or the serial communication port.
3. The [STOP], [JOG] and [RESET] keys, provided that
these are active (see parameter 014, 015 and 017).
If Local control [1] is selected, the frequency
converter can be controlled via:
1. The [START] key. However, this cannot override
Stop commands on the digital terminals (if [2] or
[4] has been selected in parameter 013).
2. The [STOP], [JOG] and [RESET] keys, provided that
these are active (see parameter 014, 015 and 017).
3. The [FWD/REV] key, provided that this has been
activated in parameter 016 and that in parameter
013 a choice of [1] or [3] has been made.
4. Via P003 the local reference can be controlled by
means of the "Arrow up" and "Arrow down" keys.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.R3.02 -
AKD 5000
5. An external control command that can be connected
to terminal 16, 17, 19, 27, 29, 32 or 33. However,
[2] or [4] must be selected in parameter 013.
See also section Shift between local and remote control.
[0]
[1]
003 Local reference
[2]
(LOCAL REFERENCE)
[3]
Value:
[4]
Par 013 set for [1] or [2]:
[5]
0 - f
MAX
Par 013 set for [3] or [4] and par. 203 = [0] set for:
Ref
- Ref
MIN
MAX
Par 013 set for [3] or [4] and par. 203 = [1] set for:
-Ref
- + Ref
MAX
Function:
This parameter allows manual setting of the
desired reference value (speed or reference for
the selected configuration, depending on the
[0]
choice made in parameter 013).
[1]
The unit follows the configuration selected in parameter
100, provided Process control, closed loop [3] or
Torque control, open loop [4] has been selected.
Description of choice:
Local [1] must be selected in parameter 002
for this parameter to be used.
The set value is saved in the case of a voltage
drop-out, see parameter 019.
In this parameter Data Change Mode is not exited
automatically (after time out).
Local reference cannot be set via the serial
communication port.
Warning: Since the value set is remembered
after the power has been cut, the motor
may start without warning when the
power is reinstated; if parameter 019 is changed
to Auto restart, use saved ref. [0].
004 Active Setup
(ACTIVE SETUP)
Value:
Factory Setup (FACTORY SETUP)
Setup 1 (SETUP 1)
Setup 2 (SETUP 2)
MAX
000.000
000.000
000.000
[0]
[1]
[2]
59