Danfoss AKD 5001 Manual page 68

Akd 5000 series, electronic controls, refrigeration and air conditioning controls, adap-kool refrigeration control systems
Table of Contents

Advertisement

For 87 Hz operation with 230/400 V motors, set
the nameplate data for 230 V. Adapt parameter
202 Output frequency high limit and parameter 205
Maximum reference to the 87 Hz application.
NB!:
If a delta connection is used, the rated
motor frequency for the delta connected
must be selected.
NB!:
If the setting in parameter 102-109 is changed,
the parameters 110-118 will return to factory
setting. If using special motor characteristics a
change in parameter 102-109 affects parameter 422.
105 Motor current (MOTOR CURRENT)
Value:
0.01 - I
AKD,MAX
Depends on the choice of motor.
Function:
The rated motor current I
M,N
frequency converter calculations i.a. of torque
and motor thermal protection.
Description of choice:
Select a value that equals the nameplate
data on the motor.
Enter the value in Ampere.
NB!:
It is important to enter the correct value, since
this forms part of the VVC
NB!:
If the setting in parameter 102-109 is changed,
the parameters 110-118 will return to factory
setting. If using special motor characteristics a
change in parameter 102-109 affects parameter 422.
106 Rated motor speed
(MOTOR NOM. SPEED)
Value:
100 - 60000 rpm (RPM)
Depends on the choice of motor.
Function:
This is where the value is selected that corresponds
to the rated motor speed n
seen from the nameplate data.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.R3.02 -
[0.01 - XXX.X]
forms part of the
plus
control feature.
[100 - 60000]
, which can be
M,N
AKD 5000
Description of choice:
The rated motor speed n
M,N
the optimal slip compensation.
NB!:
It is important to enter the correct value,
since this forms part of the VVC
feature. The max. value equals f
60. Set f
in parameter 104.
M,N
NB!:
If the setting in parameter 102-109 is changed,
the parameters 110-118 will return to factory
setting. If using special motor characteristics a
change in parameter 102-109 affects parameter 422.
107 Automatic motor adaptation, AMA
(AUTO MOTOR ADAPT)
Value:
Adaptation off (OFF)
Adaptation on, R
and X
S
S
Adaptation on, R
(ENABLE (RS))
S
Function:
If this function is used, the frequency converter
automatically sets the necessary control parameters
(parameters 108/109) with the motor stationary.
Automatic motor adaptation ensures optimum
use of the motor.
For the best possible adaptation of the frequency
converter, it is recommended to run AMA
on a cold motor.
The AMA function is activated by pressing the
[START] key after selecting [1] or [2].
See also section Automatic motor adaptation.
The section Automatic motor adaption, AMA, via
AKD software dialog shows how automatic motor
adaptation can be activated by means of AKD Software
Dialog. After a normal sequence, the display will read
"ALARM 21". Press the [STOP/RESET] key. The
frequency converter is now ready for operation.
Description of choice:
Select Enable, R
and X
S
S
converter is to be able to carry out automatic
motor adaptation of both the stator resistance
R
and the stator reactance X
S
Select Optimisation on, R
S
is to be carried out, in which only the ohmic
resistance in the system is determined.
is used i.a. for calculating
plus
control
x
M,N
[0]
( ENABLE (RS,XS))
[1]
[2]
[1] if the frequency
.
S
[2] if a reduced test
67