Fuses - Danfoss AKD 5001 Manual

Akd 5000 series, electronic controls, refrigeration and air conditioning controls, adap-kool refrigeration control systems
Table of Contents

Advertisement

Fuses

UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
AKD
Bussmann
5001
KTN-R10
5002
KTN-R10
5003
KTN-R25
5004
KTN-R20
5005
KTN-R25
5006
KTN-R30
5008
KTN-R50
5011
KTN-R60
5016
KTN-R85
5022
KTN-R125
5027
KTN-R125
380-500 V
Bussmann
5001
KTS-R6
5002
KTS-R6
5003
KTS-R10
5004
KTS-R10
5005
KTS-R15
5006
KTS-R20
5008
KTS-R25
5011
KTS-R30
5016
KTS-R40
5022
KTS-R50
5027
KTS-R60
5032
KTS-R80
5042
KTS-R100
5052
KTS-R125
5062
KTS-R150
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
Non UL compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
AKD 5001-5027
AKD 5001-5062
AKD 5032-5052
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
(symmetrical), 500 V maximum.
rms
22
AKD 5000
SIBA
Littel fuse
5017906-010
KLN-R10
5017906-010
KLN-R10
5017906-016
KLN-R15
5017906-020
KLN-R20
5017906-025
KLN-R25
5012406-032
KLN-R30
5014006-050
KLN-R50
5014006-063
KLN-R60
5014006-080
KLN-R80
2028220-125
KLN-R125
2028220-125
KLN-R125
SIBA
Littel fuse
5017906-006
KLS-R6
5017906-006
KLS-R6
5017906-010
KLS-R10
5017906-010
KLS-R10
5017906-016
KLS-R16
5017906-020
KLS-R20
5017906-025
KLS-R25
5012406-032
KLS-R30
5012406-040
KLS-R40
5014006-050
KLS-R50
5014006-063
KLS-R60
2028220-100
KLS-R80
2028220-125
KLS-R100
2028220-125
KLS-R125
2028220-160
KLS-R150
200-240 V
380-500 V
200-240 V
Ferraz-Shawmut
ATM-R10 or A2K-10R
ATM-R10 or A2K-10R
ATM-R15 or A2K-15R
ATM-R20 or A2K-20R
ATM-R25 or A2K-25R
ATM-R30 or A2K-30R
A2K-50R
A2K-60R
A2K-80R
A2K-125R
A2K-125R
Ferraz-Shawmut
ATM-R6 or A6K-6R
ATM-R6 or A6K-6R
ATM-R10 or A6K-10R
ATM-R10 or A6K-10R
ATM-R16 or A6K-16R
ATM-R20 or A6K-20R
ATM-R25 or A6K-25R
A6K-30R
A6K-40R
A6K-50R
A6K-60R
A6K-180R
A6K-100R
A6K-125R
A6K-150R
type gG
type gG
type gR
MG.50.R3.02 -

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents