NB!:
If the setting of the motor parameters does
not match the motor applied, the read-out
values will be inaccurate and may become
negative, even if the motor is not running or is
producing a positive torque.
Power, (kW), parameter 522:
The value shown is calculated on the basis of the
actual motor voltage and motor current.
The value is filtered, which means that it may take
approx. 1.3 seconds from an input value changes
until the data read-out changes values.
Power (HP), parameter 523:
The value shown is calculated on the basis of the
actual motor voltage and motor current.
The value is indicated in the form of HP.
The value is filtered, which means that approx. 1.3
seconds may pass from an input value changes
until the data read-out changes values.
Motor voltage, parameter 524:
The value shown is a calculated value used
for controlling the motor.
DC link voltage, parameter 525:
The value shown is a measured value.
The value is filtered, which means that approx. 1.3
seconds may pass from an input value changes
until the data read-out changes values.
Motor temp., parameter 526:
AKD temp., parameter 527:
Only whole numbers are displayed.
Digital input, parameter 528:
The value shown indicates the signal status from the 8
digital terminals (16, 17, 18, 19, 27, 29, 32 and 33).
The read-out is binary and the digit at the extreme left
gives the status of terminal 16, while the digit at the
extreme right gives the status of terminal 33.
Terminal 53, analogue input, parameter 529:
The value shown indicates the signal value
on terminal 53.
The scaling (parameters 309 and 310) does not
influence the read-out. Min. and max. are determined
by the offset and gain adjustment of the AD-converter.
Terminal 54, analogue input, parameter 530:
The value shown indicates the signal value
on terminal 54.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.R3.02 -
AKD 5000
The scaling (parameters 312 and 313) does not
influence the read-out. Min. and max. are determined
by the offset and gain adjustment of the AD-converter.
Terminal 60, analogue input, parameter 531:
The value shown indicates the signal value
on terminal 60.
The scaling (parameters 315 and 316) does not
influence the read-out. Min. and max. are determined
by the offset and gain adjustment of the AD-converter.
Pulse reference, parameter 532:
The value shown indicates any pulse reference in
Hz connected to one of the digital inputs.
External reference %, parameter 533:
The value stated gives, as a percentage, the sum of
external references (sum of analogue/bus/pulse).
Status word, parameter 534:
Indicates the status word transmitted via the serial
communication port in Hex code from the frequency
converter. See the Design Guide.
Heat sink temperature, parameter 537:
States the given heat sink temperature of the
frequency converter. The cut-out limit is 90 ± 5°C,
while the unit cuts back in at 60 ± 5°C.
Alarm word, parameter 538:
States in Hex format whether there is an alarm
on the frequency converter.See section Warning
word 1, Extended status word and Alarm word
for further information.
AKD control word, parameter 539:
Gives the control word sent via the serial communication
port in Hex code to the frequency converter. See
the Design Guide for further information.
Warning word, 1, parameter 540:
States in Hex format whether there is a warning
on the frequency converter. See section Warning
word 1, Extended status word and Alarm word
for further information.
Extended status word Hex, parameter 541:
States in Hex format whether there is a warning
on the frequency converter.
See section Warning word 1, Extended status word
and Alarm word for further information.
Motor RPM, parameter 557:
95