Setup 3 (SETUP 3)
Setup 4 (SETUP 4)
MultiSetup (MULTI SETUP)
Function:
This parameter defines the Setup number to control
the functions of the frequency converter.
All parameters can be programmed in four individual
parameter Setups, Setup 1 - Setup 4. In addition, there
is a Factory Setup, which cannot be modified.
Description of choice:
Factory Setup [0] contains the data set at the works.
Can be used as a data source if the other Setups
are to be returned to a known state.
Parameter 005 and 006 allow copying from one
Setup to one or all the other Setups.
Setups 1-4 [1]-[4] are four individual Setups that
can be selected individually.
Multi-Setup [5] is used by remote-switching
between Setups. Terminals 16/17/29/32/33 as
well as the serial communication port can be used
for switching between Setups.
005 Programming Setup
(EDIT SETUP)
Value:
Factory Setup (FACTORY SETUP)
Setup 1 (SETUP 1)
Setup 2 (SETUP 2)
Setup 3 (SETUP 3)
Setup 4 (SETUP 4)
Active Setup (ACTIVE SETUP)
Function:
The choice is of the Setup in which programming
(change of data) is to occur during operation
(applies both via the control panel and via the
serial communication port). The 4 Setups can be
programmed independently of the Setup selected as
the active Setup (selected in parameter 004).
Description of choice:
The Factory Setup [0] contains the data set at the
works and can be used as a data source if the other
Setups are to be returned to a known state.
Setups 1-4 [1]-[4] are individual Setups which can be
used as required. They can be programmed freely,
regardless of the Setup selected as the active Setup and
thus controlling the functions of the frequency converter.
= factory setting. () = display text [] = value for use in communication via serial communication port
60
AKD 5000
[3]
NB!:
[4]
If a general change of data or a copying to
[5]
the active Setup is effected, this immediately
affects the functioning of the unit.
006 Copying of Setups
(SETUP COPY)
Value:
No copying (NO COPY)
Copy to Setup 1 from # (COPY TO SETUP 1)
Copy to Setup 2 from # (COPY TO SETUP 2)
Copy to Setup 3 from # (COPY TO SETUP 3)
Copy to Setup 4 from # (COPY TO SETUP 4)
Copy to Setup all from # (COPY TO ALL)
# = the Setup selected in parameter 005
Function:
A copy is made from the Setup selected in parameter
005 to one of the other Setups or to all the other
Setups simultaneously. The setup copying function
does not copy parameter 001, 004, 005, 500 and 501.
Copying is only possible in Stop Mode (motor
stopped on a Stop command).
Description of choice:
The copying starts when the desired copying
[0]
function has been entered and confirmed by
[1]
pressing the [OK] key.
[2]
The display indicates when copying is in progress.
[3]
[4]
[5]
007 LCP copy
(LCP COPY)
Value:
No copying (NO COPY)
Upload all parameters (UPLOAD ALL PARAM)
Download all parameters (DOWNLOAD ALL)
Download power-independent par.
(DOWNLOAD SIZE INDEP.)
Function:
Parameter 007 is used if it is desired to use the
integrated copying function of the control panel. The
control panel is detachable. You can therefore easily
copy parameter value(s) from one to another.
Description of choice:
Select Upload all parameters [1] if all parameter values
are to be transmitted to the control panel.
[0]
[1]
[2]
[3]
[4]
[5]
[0]
[1]
[2]
[3]
MG.50.R3.02 -