Danfoss AKD 5001 Manual page 42

Akd 5000 series, electronic controls, refrigeration and air conditioning controls, adap-kool refrigeration control systems
Table of Contents

Advertisement

Tightening-up torque: 0.5-0.6 Nm
Screw size: M3
See section earthing of braided screened/armoured
control cables.
MG.50.R3.02 -
AKD 5000
No.
Function
1 1 1 1 2 2 2 2 , , , , 1 1 1 1 3 3 3 3
Voltage supply to digital inputs
For the 24 V DC to be usable
for the digital inputs, switch 4 on
the control card must be closed.
position "ON".
1 1 1 1 6 6 6 6 - - - - 3 3 3 3 3 3 3 3
Digital inputs/encoder inputs
2 2 2 2 0 0 0 0
Ground for digital inputs
3 3 3 3 9 9 9 9
Ground for analogue/digital
outputs
4 4 4 4 2 2 2 2 , , , , 4 4 4 4 5 5 5 5
Analogue/digital outputs for
indicating frequency, reference,
current and torque
5 5 5 5 0 0 0 0
Supply voltage to potentiometer
and thermistor 10 V DC
5 5 5 5 3 3 3 3 , , , , 5 5 5 5 4 4 4 4
Analogue reference input, voltage
0 - ±10 V
5 5 5 5 5 5 5 5
Ground for analogue reference
inputs
6 6 6 6 0 0 0 0
Analogue reference input, current
0/4-20 mA
6 6 6 6 1 1 1 1
Termination for serial
communication. See section
Bus connection. This terminal is
normally not to be used.
6 6 6 6 8 8 8 8 , , , , 6 6 6 6 9 9 9 9
RS 485 interface, serial
communication. Where the
frequency converter is connected
to a bus, switches 2 and 3
(switches 1- 4) must be closed
on the first and the last frequency
converter. On the remaining
frequency converters, switches 2
and 3 must be open. The factory
setting is closed (position "ON").
41