315 Terminal 60, min. scaling
(AI 60 SCALE LOW)
Value:
0.0 - 20.0 mA
Function:
This parameter determines the value of the reference
signal that is to correspond to the minimum
reference value set in parameter 204.
If the Time-out function of parameter 317 is used,
the value must be set at >2 mA.
Description of choice:
Set the desired current value.
See also section Handling of single references.
316 Terminal 60, max. scaling
(AI 60 SCALE HIGH)
Value:
0.0 - 20.0 mA
Function:
This parameter sets the value of the reference
signal that is to correspond to the maximum
reference value set in parameter 205.
Description of choice:
Set the desired current value.
See also section Handling of single references .
317 Time out
(LIVE ZERO TIME O)
Value:
0 - 99 sec.
Function:
If the signal value of the reference signal connected
to the input, terminal 60, falls below 50% of the
value set in parameter 315 for a period longer than
the time set in parameter 317, the function selected
in parameter 318 will be activated.
Description of choice:
Set the desired time.
318 Function after time out
(LIVE ZERO FUNCT.)
Value:
Off (OFF)
Freeze output frequency (FREEZE OUTPUT FREQ.) [1]
= factory setting. () = display text [] = value for use in communication via serial communication port
82
AKD 5000
Stop (STOP)
Jog (JOGGING)
Max. speed (MAX SPEED)
Stop and trip (STOP AND TRIP)
0.0 mA
Function:
This parameter allows a choice of the function to
be activated if the input signal on terminal 60 drops
below 2 mA, provided parameter 315 has been set
higher than 2 mA and that the preset time for time-out
(parameter 317) has been exceeded.
If more time-outs occur at the same time the
frequency converter will give the following priority
to the time-out function:
1. Parameter 318 Function after time out
2. Parameter 514 Bus time interval function
Description of choice:
The output frequency of the frequency converter can be:
- frozen at the present value
- overruled to stop
20.0 mA
- overruled to jog frequency (10 Hz)
- overruled to max. frequency
- overruled to stop with subsequent trip.
10 sec.
[0]
[2]
[3]
[4]
[5]
MG.50.R3.02 -