Danfoss AKD 5001 Manual page 111

Akd 5000 series, electronic controls, refrigeration and air conditioning controls, adap-kool refrigeration control systems
Table of Contents

Advertisement

Warning word 1, Extended status word
and Alarm word
The warning word 1, extended status word and
the alarm word return the different status, warning
and alarm messages of the frequency converter as
hexdecimal value. If there are more than one warning
or alarm, a sum of all warnings or alarms will be shown.
Warning word 1, extended status word and alarm
word can also be displayed using the serial bus
in parameter 540, 541 and 538.
B B B B i i i i t t t t ( ( ( ( H H H H e e e e x x x x ) ) ) ) W W W W a a a a r r r r n n n n i i i i n n n n g g g g w w w w o o o o r r r r d d d d 1 1 1 1 ( ( ( ( p p p p a a a a r r r r a a a a m m m m e e e e t t t t e e e e r r r r 5 5 5 5 4 4 4 4 0 0 0 0 ) ) ) )
000002 EE-prom power card fault
000004 EE-prom control card
000008 HPFP bus timeout
000010 Standard bus timeout
000020 Overcurrent
000040 Torque limit
000080 Motor thermistor
000100 Motor overload
000200 Inverter overload
000400 Undervoltage
000800 Overvoltage
001000 Voltage warning low
002000 Voltage warning high
004000 Phase fault
008000 No motor
010000 Live zero fault
(4-20 mA current signal low)
020000 10 Volts low
040000
400000 Out of frequency range
800000 Fieldbus communication fault
1000000
2000000 Mains failure
4000000 Motor too small
8000000 Motor too big
10000000 Check P. 103 and P. 105
20000000 Check P. 104 and P. 106
40000000 Encoder loss
B B B B i i i i t t t t ( ( ( ( H H H H e e e e x x x x ) ) ) ) E E E E x x x x t t t t e e e e n n n n d d d d e e e e d d d d s s s s t t t t a a a a t t t t u u u u s s s s w w w w o o o o r r r r d d d d ( ( ( ( p p p p a a a a r r r r a a a a m m m m e e e e t t t t e e e e r r r r
5 5 5 5 4 4 4 4 1 1 1 1 ) ) ) )
000001 Ramping
000002 Automatic motor tuning
000004 Start clockwise/anti-clockwise
000008 Slow down
000010 Catch-up
000020 Feedback high
000040 Feedback low
000080 Output current high
000100 Output current low
000200 Output frequency high
000400 Output frequency low
004000 Quick discharge OK
008000 Out of frequency range
110
AKD 5000
B B B B i i i i t t t t ( ( ( ( H H H H e e e e x x x x ) ) ) ) A A A A l l l l a a a a r r r r m m m m w w w w o o o o r r r r d d d d 1 1 1 1 ( ( ( ( p p p p a a a a r r r r a a a a m m m m e e e e t t t t e e e e r r r r 5 5 5 5 3 3 3 3 8 8 8 8 ) ) ) )
000001 Brake test failed
000002 Trip locked
000004 AMA tuning not OK
000008 AMA tuning OK
000010 Power-up fault
000020 ASIC fault
000040 HPFP bus timeout
000080 Standard bus timeout
000100 Short-circuiting
000200 Switchmode fault
000400 Earth fault
000800 Overcurrent
001000 Torque limit
002000 Motor thermistor
004000 Motor overload
008000 Inverter overload
010000 Undervoltage
020000 Overvoltage
040000 Phase fault
080000 Live zero fault (4 - 20 mA current
signal low)
100000 Heat sink temperature too high
200000 Motor phase W missing
400000 Motor phase V missing
800000 Motor phase U missing
1000000 Quick discharge not ok
2000000 Fieldbus communication fault
4000000 Mains failure
8000000 Inverter fault
20000000 Encoder loss
40000000 Safety interlock
80000000 Reserved