Service and Troubleshooting
November 2017
LCD display
Host diagnostic
message
message
HIGH
High User Defined Alert
ALERT
LOW
Low User Defined Alert
ALERT
VAR
Linearized Variable Out of
OUTRNG
Range
DC
Dielectric Constant
DEGRAD
Estimation Degraded
86
Description
The user defined variable is above the
defined limit.
The user defined variable is below the
defined limit.
The level measurement is outside the
configured range for volume or scaled
variable, or both.
Accuracy of volume/scaled variable
measurement may be degraded.
The dielectric constant estimation is
degraded.
Accuracy of level measurement may be
degraded.
Reference Manual
00809-0100-4408, Rev BA
Recommended actions
1. Bring the system to a safe state.
2. Verify that the process variable is within
specified limits.
3. Reconfirm the user defined alarm limit.
4. If not needed, disable this alert.
1. Bring the system to a safe state.
2. Verify that the process variable is within
specified limits.
3. Reconfirm the user defined alarm limit.
4. If not needed, disable this alert.
1. If volume strapping table is used, make
sure level values within operating
range are included.
2. If scaled variable table is used, make
sure input variable values within
operating range are included.
1. Check configuration of Bottom Product
Dielectric Constant.
2. Check configuration of Reference
Height and Bottom Offset.
3. If not needed, disable Tank Bottom
Projection.
Service and Troubleshooting