Emerson Rosemount 5408 Reference Manual page 183

Level transmitters. non-contacting radar
Hide thumbs Also See for Rosemount 5408:
Table of Contents

Advertisement

Reference Manual
00809-0100-4408, Rev BA
3. Appropriate cable, glands, and plugs need to be suitable for a
temperature of 5°C greater than the maximum specified
ambient temperature for location where installed.
4. The Transmitter can be installed in the boundary wall
between a Zone 0 and Zone 1 area. In this configuration, the
process connection is installed in Zone 0, while the
transmitter housing is installed in Zone 1. Refer to Control
Drawing D7000002-885.
5. Cable entries must be used which maintain the ingress
protection of the enclosure to at least IP6X and/or Type 4X
rating. To maintain the ingress protection ratings. Covers and
Sensor Module to be fully tightened and PTFE tape or pipe
dope is required for cable entries and blanking plugs. See
Instruction Manual on application requirements.
6. Install per Control drawing D7000002-885.
7. Using the box provided on the nameplate, the User shall
permanently mark the type of protection chosen for the
specific installation. Once the type of protection has been
marked it shall not be changed.
8. Display glass shall be positioned in such a way as to minimize
the risk of mechanical impact.
9. The applicable temperature class, ambient temperature
range and process temperature range of the equipment is as
follows;
For Divisions:
Temperature class /
Ambient
Maximum surface
temperature
temperature
range
Division Gas groups:
-40°C ≤ Ta ≤ 70°C
T2
-40°C ≤ Ta ≤ 70°C
T3
-40°C ≤ Ta ≤ 70°C
T4
-40°C ≤ Ta ≤ 70°C
T5
-40°C ≤ Ta ≤ 70°C
T6
Division Dust groups:
-50°C ≤ Ta ≤ 70°C
T3
-50°C ≤ Ta ≤ 70°C
T4
-50°C ≤ Ta ≤ 70°C
T5
-50°C ≤ Ta ≤ 70°C
T6
Product Certifications
For Zones:
Temperature class /
Maximum surface
temperature
Zone Gas groups:
T2
T3
T4
T5
T6
Zone Dust groups:
T250°C
T200°C
T135°C
T100°C
T85°C
I5
Process
temperature
range
-40°C to 250°C
-40°C to 195°C
-40°C to 130°C
-40°C to 95°C
-40°C to 80°C
-50°C to 160°C
-50°C to 130°C
Safety parameter
-50°C to 95°C
Voltage U
-50°C to 80°C
Current I
Power P
Capacitance C
Inductance L
Ambient
temperature
range
-50°C ≤ Ta ≤ 70°C
-50°C ≤ Ta ≤ 70°C
-50°C ≤ Ta ≤ 70°C
-50°C ≤ Ta ≤ 70°C
-50°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
FM Intrinsic Safety (IS), Non-Incendive (NI)
Certificate: FM16US0010X
Standards: FM Class 3600 – 2011; FM Class 3610 – 2015; FM
Class 3611 – 2016; FM Class 3810 – 2005;
ANSI/ISA 60079-0 – 2013; ANSI/ISA 60079-11 –
2013; ANSI/ISA 60079-26 – 2011; ANSI/NEMA
250 – 1991; ANSI/IEC 60529 – 2004; ANSI/ISA
12.27.01:2011
Markings: IS CL I, ll, lll DIV 1, GRPS A-G T4...T2
NI CL I, DIV 2, GRPS A-D T4...T2
S CL Il, lll DIV 2, GRPS E-G T4...T3
CL l Zone 0 AEx ia IIC T4...T2 Ga
CL l Zone 0/1 AEx ib IIC T4...T2 Ga/Gb
Zone 20 AEx ia IIIC T85°C...T250°C Da
(-60°C ≤ Ta ≤ +70°C)
When installed per Control Drawing
D7000002-885
SINGLE SEAL
HART
30 V
i
133 mA
i
1.0 W
i
7.3 nF
i
0
i
Product Certifications
November 2017
Process
temperature
range
-50°C to 250°C
-50°C to 195°C
-50°C to 130°C
-50°C to 95°C
-50°C to 80°C
-60°C to 250°C
-60°C to 195°C
-60°C to 130°C
-60°C to 95°C
-60°C to 80°C
®
171