Service and Troubleshooting
November 2017
(1)
Symptom
Measured level is correct at 0% (4 mA) but
incorrect at 100% (20 mA).
Incorrect level when the product surface is
above the 50% level.
Measured value drops to zero level.
When the product surface is near the sloped
tank bottom, the transmitter enters alarm
mode.
1.
= actual level
= reported level
90
Possible causes
Upper Range Value is not set
correctly.
Time
Strong double bounce echo
that is interpreted as the
product surface.
Time
Transmitter has locked on a
strong tank bottom echo.
Time
Reduction of projected surface
area close to sloping tank
bottom.
Time
Reference Manual
00809-0100-4408, Rev BA
Recommended actions
Check that the Upper Range Value matches the
100% (20 mA) level in the tank.
Enable the Double Bounce Handling function, see
"Handling strong double bounce echoes" on
page
111.
Verify the Reference Height is configured
correctly.
Enable the Tank Bottom Projection function, see
"Use tank bottom projection" on page
Enable the Bottom echo visible when tank is empty
parameter, see
"Enable bottom echo visible
when tank is empty" on page
Verify the tank geometry parameters are
configured correctly (especially the Reference
Height and Bottom Offset).
If measurement in this region is not crucial,
increase the Empty Tank Detection Area, see
"Empty tank detection area" on page
Verify the Bottom echo visible when tank is empty
parameter is disabled, see
when tank is empty" on page
Service and Troubleshooting
108.
108.
200.
"Bottom echo visible
201.