Product Certifications
November 2017
Specific Conditions of Use (X):
1. The Model 5408 Level Transmitter will not pass the 500Vrms
dielectric strength test between the circuits and the earth
ground. This must be taken into account during installation.
2. Plastic wire-on tag, Plastic part of Process Seal Antenna and
Non-standard paint options (paint options other than
Rosemount Blue) may cause risk from Electrostatic
discharge. Avoid installation that could cause electrostatic
build-up, and only clean with a damp cloth.
3. Appropriate cable, glands, and plugs need to be suitable for a
temperature of 5°C greater than the maximum specified
ambient temperature for location where installed.
4. The Transmitter can be installed in the boundary wall
between a Zone 0 and Zone 1 area. In this configuration, the
process connection is installed in Zone 0, while the
transmitter housing is installed in Zone 1. Refer to Control
Drawing D7000002-885.
5. Using the box provided on the nameplate, the User shall
permanently mark the type of protection chosen for the
specific installation. Once the type of protection has been
marked it shall not be changed.
6. The applicable temperature class, ambient temperature
range and process temperature range of the equipment is as
follows;
For Divisions:
Temperature class /
Ambient
Maximum surface
temperature
temperature
range
Division Gas groups:
-60°C ≤ Ta ≤ 70°C
T2
-60°C ≤ Ta ≤ 70°C
T3
-60°C ≤ Ta ≤ 70°C
T4
Division Dust groups:
-60°C ≤ Ta ≤ 70°C
T3
-60°C ≤ Ta ≤ 70°C
T4
-60°C ≤ Ta ≤ 70°C
T5
-60°C ≤ Ta ≤ 70°C
T6
174
For Zones:
Temperature class /
Maximum surface
temperature
Zone Gas groups:
T2
T3
T4
Zone Dust groups:
T250°C
T200°C
T135°C
T100°C
T85°C
B.10 Europe
E1
Process
temperature
range
Specific Conditions of Use (X):
-60°C to 250°C
1. Flamepath joints are not for repair. Contact the
-60°C to 195°C
-60°C to 130°C
2. Plastic wire-on tag, Plastic part of Process Seal Antenna and
-60°C to 160°C
-60°C to 130°C
3. Appropriate cable, glands, and plugs need to be suitable for a
-60°C to 95°C
-60°C to 80°C
4. The Transmitter can be installed in the boundary wall
5. Cable entries must be used which maintain the ingress
6. Install per Control Drawing D7000002-885.
Ambient
temperature
range
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
-60°C ≤ Ta ≤ 70°C
ATEX Flameproof
Certificate: FM15ATEX0055X
Standards: EN 60079-0:2012, EN 60079-1:2014, EN
60079-26:2015, EN 60079-31:2014, EN
60529+A1+A2:2013
Markings:
II 1/2G Ex db IIC T6...T2 Ga/Gb
II 2D Ex tb IIIC T85°C... T250°C Db, IP6X
(-60°C ≤ Ta ≤ +70 °C)
manufacturer.
Non-standard paint options (paint options other than
Rosemount Blue) may cause risk from Electrostatic
discharge. Avoid installation that could cause electrostatic
build-up, and only clean with a damp cloth.
temperature of 5°C greater than the maximum specified
ambient temperature for location where installed.
between a Category 1 and Category 2 location. In this
configuration, the process connection is installed in
Category 1, while the transmitter housing is installed in
Category 2. Refer to Control Drawing D7000002-885.
protection of the enclosure to at least IP6X. To maintain the
ingress protection ratings. Covers and Sensor Module to be
fully tightened and PTFE tape or pipe dope is required for
cable entries and blanking plugs. See Instruction Manual on
application requirements
Reference Manual
00809-0100-4408, Rev BA
Process
temperature
range
-60°C to 250°C
-60°C to 195°C
-60°C to 130°C
-60°C to 250°C
-60°C to 195°C
-60°C to 130°C
-60°C to 95°C
-60°C to 80°C
Product Certifications