3.3.8

Still pipe/chamber installations

Installation in still pipe/chamber is recommended for tanks where there are excessive foaming or
turbulence. Still pipe/chamber may also be used to avoid disturbing objects in the tank.
All cone/process seal antenna sizes can be used for still pipe/chamber installations.
Still pipe
Consider the following still pipe requirements:
Pipe
Pipes should be an all-metal material.
Pipe should have a constant inside diameter.
The inner surface must be smooth and clear of any rough edges.
(Smooth pipe joints are acceptable, but may reduce accuracy.)
The end of the pipe must extend beyond the zero level.
Holes
Maximum hole diameter is 1 in. (25 mm).
Minimum distance between holes is 6 in. (150 mm).
Holes should be drilled on one side only and deburred.
Drill one hole above maximum product surface.
Antenna
The gap between the cone antenna and the still pipe should be maximum 0.2 in. (5 mm). If required,
order a larger antenna and cut on location. See
Figure 3-9. Still Pipe Requirements
Level = 100%
Level = 0%
Mechanical Installation
Max. 1°
Max. 1 in. (25 mm)
Min. 6 in. (150 mm)
Figure A-10 on page 163
Max. 0.2 in.
(5 mm)
Mechanical Installation
November 2017
for antenna dimensions.