Configuration Parameters
November 2017
Figure C-18. Signal Quality Alert
A.
The Signal Quality drops below the alert limit and an alert message is triggered.
B.
The alert message is reset once the Signal Quality value rises above the Deadband range.
Limit
The Signal Quality value that will trigger the alert.
Deadband
The Deadband is a buffer zone so the alerts do not toggle on and off when the Signal Quality fluctuates
around the alert limit. The alert is set when value falls below the alert limit. The alert is then cleared when
value rises above the Deadband range.
C.4.3

High/low user defined alert

A high and low alert may be established to output an alert message when the measurement readings
exceed the specified limits.
Variable
Select the transmitter variable to use for the alert.
Limit
The value that will trigger the alert.
Deadband
The Deadband is a buffer zone so the alerts do not toggle on and off when the measurement value
fluctuates around the alert limit. The alert is set when the value exceeds the alert limit. The alert is then
cleared when the value falls outside the Deadband range, see
204
Alert ON
B
A
Time
Reference Manual
00809-0100-4408, Rev BA
Deadband
Limit
Figure C-19
and
Figure
Configuration Parameters
C-20.