Reference Manual
00809-0100-4408, Rev BA
LCD display
Host diagnostic
message
message
CONFG
Configuration Error
ERROR
Table 7-2. Configuration Error Details
Host diagnostic message
Volume Configuration Error
Scaled Variable Configuration
Error
Geometry Configuration Error
Primary Variable Configuration
Error
Measurement Correction
Configuration Error
Threshold Configuration Error
Service and Troubleshooting
Description
The device has detected a configuration
error. Reasons may be multiple (see
Table 7-2
for details).
Description
The volume cannot be calculated correctly
with the current configuration.
The Scaled Variable configuration is
incorrect.
The configured tank geometry results in a
too large level measuring range for this
device.
The Primary Variable selection is not
supported.
Note
Rosemount
5408:SIS only supports level
or distance as Primary Variable.
The factory measurement correction data
is invalid.
The surface threshold configuration is
incorrect.
Service and Troubleshooting
Recommended actions
1. Click the Details button for more
information.
2. Correct the parameter causing the
error.
Recommended actions
1. If strapping table is used, check that level-volume
values are entered in increasing order.
2. If strapping table is used, check that number of
strapping points to use is correct.
3. If tank dimensions are used for volume, check
that geometry shape and size measures are
correct.
4. If condition persists, restore default settings and
reconfigure the device.
1. Check that the value pairs in the scaled variable
table are entered in increasing order.
2. Check the number of table points to use is
correct.
3. If condition persists, restore default settings, and
reconfigure the device.
1. Check tank geometry configuration and reduce
Reference Height.
2. If condition persists, restore default settings and
reconfigure the device.
1. Change Primary Variable to variable supported by
device.
2. Consider purchasing an upgrade of the device to
access additional variables.
1. Restore default settings and reconfigure the
device.
2. If the condition persists, replace the device.
1. In the threshold table, check that
distance-threshold values are entered in
increasing order.
2. Check that the number of threshold points to use
is correct.
3. If condition persists, restore default settings and
reconfigure the device.
November 2017
83