Technical specifications
12.1 Technical specifications
min. DMS output resistance
Temperature coefficient range
Temperature coefficient zero point
Linearity error
Measured value filtering
Electrical isolation
50 Hz / 60 Hz noise suppression CMRR
Input resistance
Relative accuracy! (Absolute accuracy is only reached by calibration on-site with calibration stand-
1)
ard)
2)
3)
Analog output
The set replacement value is output in case of a fault or SIMATIC CPU stop.
Table 12- 3
Error limit according to DIN 1319-1 of full-scale
value at 20 °C +10 K
Refresh rate
Resolution
Measuring ranges
Max. output current
Error signal (if configured (FW))
Max. load
Temperature coefficient range
Temperature coefficient zero point
Linearity error
Electrical isolation
Cable length
Figure 12-1
172
Accuracy for module replacement or theoretical calibration decisive
Value valid at sensor; voltage drops on cables are compensated up to 5 V
Technical specifications:
Current ranges for signal level to Namur recommendation NE43
50 Ω
with Ex-i inter-
face SIWAREX
IS
4 100 Ω
≤ ± 5 ppm/K v. E.
≤ ± 0.1 μV/K
≤ 0.002 %
Low pass
500 V AC
> 80 dB
typ. 5*10
Signal cable
typ. 5*10
Sensor cable
0 ... 20 mA: ≤ 0.5 %
4 mA to 20 mA: ≤ 0.3 %
≤ 100 ms
14 bit
0 mA to 20 mA
4 mA to 20 mA
24 mA
22 mA
600 Ω
≤ ± 25 ppm/K v. E.
typ. ± 0.3 μA/K
≤ 0.05 %
500 V AC
max. 100 m, twisted and shielded
Ω
6
Ω
6