Error state
1.5.2 Analogue output
Range
Source
Start value (0/4mA)
End value (20mA)
State by error or
stop
1.5.3 Remote totalizer pulse signal
SIWAREX WT241
Manual, 05/2015, A5E36046748A
This parameter allows you to define the response of the digital in- and
outputs following a fault of the SIWAREX module
The following values can be set:
All „FALSE" – All outputs are switched off
Obtain functionality
Defined value -- The relevant substitute value is activated
All „TRUE" -- Outputs are switched on
SIWAREX WT241 is providing one analogue output which is parameterized
in menu 1.5.2.
This parameter is used to define the output current range.
The following values can be set:
0 ... 20 mA
4 ... 20 mA
The analog output can be used for a range of purposes. This parameter
defines the tag that controls the analog output.
The following values can be set:
Belt speed
Belt load
Flow rate
Test / force output
This parameter defines the specified value at which 0 or 4 mA is output.
The value can be greater or less than the end value.
This parameter defines the specified value at which 20 mA is output.
The value can be greater or less than the start value.
This parameter defines the response of the analog output following a
fault of the SIWAREX module.
The following values can be set:
Min. (0mA)
Obtain functionality
Defined value
Max. (24mA)
By parameterizing the corresponding digital output you can use one of the
digital outputs as a pulse sensor/quantity (see 8.7 "Menu 1.5 Communica-
tion & interfaces" 68).
In addition you must specify a load per pulse and a pulse duration for the
signal. If the material flow rate is displayed e.g. in t/h, you must specify the
quantity per pulse in t, or with kg/h in kg. The pulse duration is defined in
ms.
Make sure when setting the parameters that you only enter plausible com-
Scale parameters and functions of the belt scale